English
Language : 

DRM-24V80W1PN Datasheet, PDF (8/20 Pages) Delta Electronics, Inc. – Built-in active PFC and up to 90% efficiency
TECHNICAL DATASHEET
CliQ M DIN Rail Power Supply
24V 81.6W 1 Phase / DRM-24V80W1PN
EMC
Emissions
(CE & RE)
Component Power Supply for General
Use
Immunity
Electrostatic Discharge
Radiated Field
Electrical Fast Transient / Burst
Surge
Conducted
Power Frequency Magnetic
Fields
Voltage Dips and Interruptions
Low Energy Pulse Test
(Ring Wave)
Harmonic Current Emission
Voltage Fluctuation and Flicker
Voltage Sag Immunity
SEMI F47 – 0706
Generic Standards: EN 61000-6-3
CISPR 22, EN 55022, CISPR 11, EN 55011, FCC Title 47: Class B
EN 61204-3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
EN 55024, EN 61000-6-2
Level 4 Criteria A1)
Air Discharge: 15kV
Contact Discharge: 8kV
Level 3 Criteria A1)
80MHz-1GHz, 10V/M, 80% modulation (1kHz)
1.4GHz-2GHz, 10V/M, 80% modulation (1KHz)
2GHz-2.7GHz, 10V/M, 80% modulation (1KHz)
Level 4 Criteria A1)
4kV
Level 4 Criteria A1)
Common Mode3): 4kV
Differential Mode4): 2kV
Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Criteria A1)
30A/Meter
0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0% of 200Vac
Level 3 Criteria A1)
Common Mode3): 2kV
Differential Mode4): 1kV
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
0Vac, 5000ms
IEC/EN 61000-3-2, Class A
IEC/EN 61000-3-3
80% of 120Vac
70% of 120Vac
50% of 120Vac
96Vac, 1000ms
84Vac, 500ms
60Vac, 200ms
Criteria A1)
Criteria B2)
Criteria A1)
Criteria A1)
Criteria A1)
Criteria A1)
Criteria B2)
Criteria A1)
Criteria A1)
Criteria A1)
1) Criteria A: Normal performance within the specification limits
2) Criteria B: Temporary degradation or loss of function which is self-recoverable
3) Asymmetrical: Common mode (Line to earth)
4) Symmetrical: Differential mode (Line to line)
8
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (May 2016, Rev. 00)