DRM-24V80W1PN Datasheet, PDF (4/20 Pages) Delta Electronics, Inc. – Built-in active PFC and up to 90% efficiency
TECHNICAL DATASHEET
CliQ M DIN Rail Power Supply
24V 81.6W 1 Phase / DRM-24V80W1PN
Output Ratings / Characteristics**
Nominal Output Voltage
Factory Set Point Tolerance
Output Voltage Adjustment Range
Output Current
Nom.
Nom.
24Vdc
± 1.0% (initial set point tolerance from factory)
24-28Vdc
3.4A / 3.0A
5.0A / 4.5A
(Slew rate 0.1A/µs)
Continuously operating at 24V / 28V
Power Boost for 5 seconds at 24V / 28V,
refer to the details in the Function section
Output Power
Power Boost Duration
Power Boost Recovery Time
Advanced Power Boost
(Slew rate 0.1A/µs)
Nom. 81.6W / 84W
Nom. 120W / 126W
Typ. 5 seconds
Max. 7 seconds
Typ. 14 seconds
Typ. 6.8A @ 50ms, resistive load
Typ. 13.5A @ 2ms, resistive load
Typ. 13.5A @ 5ms, resistive load
Continuously operating at 24V / 28V
Power Boost for 5 seconds at 24V / 28V,
refer to the details in the Functions
section
Duration after which output voltage start
to droop, refer to the details in the
Function section at Overload &
Overcurrent Protections
Required wait duration before next Power
Boost is taken, refer to the details in the
Function section
Output voltage will drop (Refer to the
details in the Function section)
Line Regulation
Load Regulation
PARD***
Max.
Max.
Max.
10mV (@ 85-276Vac input, 100% load)
100mV (@ 85-276Vac input, 0-100% load)
50mVpp
20Hz to 20MHz, 50Ohm, warm up for
10mins
**For power de-rating from 60°C to 70°C, see power de-rating on page 10.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1μF ceramic capacitor & 47μF electrolytic capacitor.
Rise Time
Start-up Time
Hold-up Time
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
Output Capacitance
Functional
100Vac 120Vac 230Vac
Max.
Max.
Max.
430ms
15ms
55ms
370ms
0µF, 24V, 3.4A.
5,000µF, 24V, 10A.
330ms At 24V, 3.4A.
Typ. 79ms 78ms 222ms At 24V, 1.7A.
Min. 70ms 70ms 90ms At 24V, 1.7A.
Typ. 40ms 40ms 118ms At 24V, 3.4A.
Min.
Max.
35ms 35ms 70ms
± 5% @ 0-100% load
At 24V, 3.4A.
Slew rate 0.1A/µs
(@ 5Hz, 50Hz & 1kHz, 50% Duty Cycle)
Max. 8,000µF
Typ. 2,150 µF
Built-in output capacitors
DC OK Relay Rated: 30V at 1A, resistive load
Contact The relay contact are normally “ON” (closed) when the output (Vout) is
greater than 90% of its rated value.
4
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.