TECHNICAL DATASHEET
CliQ M DIN Rail Power Supply
24V 81.6W 1 Phase / DRM-24V80W1PN
Fig. 11 DC Input Operation Connection Diagram
 DC Input Operation
Step 1.
Use a battery or similar DC source.
Step 2.
Connect +pole to L and -pole to N.
Step 3.
Connect the PE terminal to an earth wire or to the machine ground.
Fig. 12 2 of 3 Phase System Input Operation Connection Diagram
 2 of 3 Phase System Input Operation
Delta's CliQ M can use on 2 of 3 phase system. Please refer to the following step.
Step 1.
The supplying voltage is below the maximum rated input. The input voltage shall be below 240Vac +10%.
Step 2.
The external protector is needed on N input line to secure a safety. N line has no protection of a fuse internally. An appropriate fuse or
circuit breaker should be connected on N input line like the following.
19
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (May 2016, Rev. 00)