English
Language : 

DRM-24V80W1PN Datasheet, PDF (2/20 Pages) Delta Electronics, Inc. – Built-in active PFC and up to 90% efficiency
TECHNICAL DATASHEET
CliQ M DIN Rail Power Supply
24V 81.6W 1 Phase / DRM-24V80W1PN
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Input Frequency
Nominal DC Input Voltage
DC input Voltage Range*
Input Current
Efficiency
Average Efficiency
Max Power Dissipation
Max Inrush Current (Cold Start)
Max Inrush Energy (Cold Start)
Power Factor
Crest Factor
Leakage Current
(Enclosure to Neutral)
*Safety approval according to IEC/EN/UL 60950-1.
100-240Vac
Nom.
85-276Vac
50-60Hz
110-300Vdc
88-375Vdc
Applicable for TN-, TT and IT mains
networks
Continuously operating
±3% range (47-63Hz)
Continuously operating
Typ.
Max.
Typ.
Min.
Typ.
Min.
Typ.
Max.
Typ.
Max.
Typ.
Max.
Max.
Typ.
Min.
Max.
100Vac 120Vac
0.91A 0.76A
1.0A
0.9A
90.95% 91.49%
87.10% 90.10%
89.78% 89.46%
88.00% 88.60%
1.19W 1.19W
1.5W 1.5W
8.16W 7.63W
9.5W 8.8W
4.08A 4.44
6.0A
7.0A
2A2s
0.99
0.98
0.95
0.95
2.1
2.1
< 0.14mA / 0.33mA
< 0.20mA / 0.46mA
< 0.36mA / 0.95mA
230Vac
0.44A At 24V, 3.4A. Refer to Fig. 1
0.6A At 24V, 3.4A.
91.31% At 24V, 3.4A. Refer to Fig. 2
90.00% At 24V, 3.4A.
89.64% At 24V, 0.85A (25% load), 1.7A (50%
88.30% load), 2.55A (75% load)
1.29W At 24V, 0A. Refer to Fig. 3
1.5W At 24V, 0A.
7.81W At 24V, 3.4A. Refer to Fig. 3
9.1W At 24V, 3.4A.
12.3A Entire temperature range
13.0A
0.89 At 24V, 3.4A. Refer to Fig. 4
0.8 At 24V, 3.4A.
2.1 At 24V, 3.4A.
110Vac, 50Hz, TN/TT system / IT system
132Vac, 50Hz, TN/TT system / IT system
264Vac, 50Hz, TN/TT system / IT system
2
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (May 2016, Rev. 00)