BCM6123XD1E5126YZZ Datasheet, PDF (15/30 Pages) Vicor Corporation – Isolated Fixed-Ratio DC-DC Converter
BCM6123xD1E5126yzz
PMBus™ Reported Characteristics
Specifications apply over all line, load conditions, unless otherwise noted; boldface specifications apply over the temperature range of
-40°C ≤ TINTERNAL ≤ 125°C (T-Grade); All other specifications are at TINTERNAL = 25ºC unless otherwise noted.
Monitored Telemetry
• The BCM communication version is not intended to be used without a Digital Supervisor.
ATTRIBUTE
DIGITAL SUPERVISOR
PMBusTM READ COMMAND
ACCURACY
(RATED RANGE)
FUNCTIONAL
UPDATE
REPORTING RANGE RATE
REPORTED UNITS
Input voltage
(88h) READ_VIN
± 5% (LL - HL)
130V to 450V
Input current
(89h) READ_IIN
± 20% (10 - 20% of FL)
± 5% (20 - 133% of FL)
-4.6A to 4.6A
Output voltage [1]
(8Bh) READ_VOUT
± 5% (LL - HL)
16.25V to 56.25V
Output current
Output resistance
(8Ch) READ_IOUT
(D4h) READ_ROUT
± 20% (10 - 20% of FL)
± 5% (20 - 133% of FL)
± 5% (50 - 100% of FL) at NL
± 10% (50 - 100% of FL) (LL - HL)
-37A to 37A
10mΩ to 40mΩ
Temperature [2]
(8Dh) READ_TEMPERATURE_1
± 7°C (Full Range)
[1] Default READ Output Voltage returned when unit is disabled = -300 V.
[2] Default READ Temperature returned when unit is disabled = -273°C.
- 55ºC to 130ºC
100µs
VACTUAL = VREPORTED x 10-1
100µs
IACTUAL = IREPORTED x 10-3
100µs
VACTUAL = VREPORTED x 10-1
100µs
IACTUAL = IREPORTED x 10-2
100ms RACTUAL = RREPORTED x 10-5
100ms
TACTUAL = TREPORTED
Variable Parameter
• Factory setting of all below Thresholds and Warning limits are 100% of listed protection values.
• Variables can be written only when module is disabled either EN pulled low or VIN < VIN_UVLO-.
• Module must remain in a disabled mode for 3ms after any changes to the below variables allowing ample time to commit changes to EEPROM.
ATTRIBUTE
DIGITAL SUPERVISOR
PMBusTM COMMAND [3]
CONDITIONS / NOTES
Input / Output Overvoltage
Protection Limit
(55h) VIN_OV_FAULT_LIMIT
VIN_OVLO- is automatically 3%
lower than this set point
Input / Output Overvoltage
Warning Limit
(57h) VIN_OV_WARN_LIMIT
Input / Output Undervoltage
Protection Limit
(D7h) DISABLE_FAULTS
Can only be disabled to a preset
default value
Input Overcurrent Protec-
tion Limit
(5Bh) IIN_OC_FAULT_LIMIT
Input Overcurrent
Warning Limit
(5Dh) IIN_OC_WARN_LIMIT
Overtemperature Protection
Limit
(4Fh) OT_FAULT_LIMIT
Overtemperature
Warning Limit
(51h) OT_WARN_LIMIT
Turn on Delay
(60h) TON_DELAY
Additional time delay to the
Undervoltage Startup Delay
[3] Refer to Digital Supervisor datasheet for complete list of supported commands.
ACCURACY
(RATED RANGE)
± 5% (LL - HL)
± 5% (LL - HL)
± 5% (LL - HL)
± 20% (10 - 20% of FL)
± 5% (20 - 133% of FL)
± 20% (10 - 20% of FL)
± 5% (20 - 133% of FL)
± 7°C (Full Range)
± 7°C (Full Range)
± 50µs
FUNCTIONAL
REPORTING
RANGE
DEFAULT
VALUE
130V to 435V 100%
130V to 435V 100%
130V or 260V 100%
0 to 4.375A
100%
0 to 4.375A
100%
0 to 125°C
100%
0 to 125°C
100%
0 to 100ms
0ms