English
Language : 

PISA11.CLASS2 Datasheet, PDF (14/19 Pages) PULS GmbH – PROTECTION MODULE 24V, 4 OUTPUTS
PISA11-Series
PISA11.CLASS2
PROTECTION MODULE 24V, 4 OUTPUTS
17. EMC
This protection module is suitable for applications in industrial environment as well as in residential, commercial and
light industry environment. A detailed EMC report is available on request.
EMC Immunity
Generic standards: EN 61000-6-1 and EN 61000-6-2
Outputs
ON
Electrostatic discharge
EN 61000-4-2 Contact discharge *)
8kV
Air discharge
8kV
Electromagnetic RF field
EN 61000-4-3 80MHz-2,7GHz
10V/m
Fast transients (Burst)
EN 61000-4-4 Input lines
2kV
output lines
2kV
DC-OK, Inhibit
1kV
Surge voltage on
input lines
EN 61000-4-5
+Æ-
+/- Æ DIN-Rail
500V
1kV
Surge voltage on
output lines
Surge voltage on
signal lines
EN 61000-4-5
EN 61000-4-5
+Æ-
+/- Æ DIN-Rail
DC-OK Æ DIN-Rail
500V
1kV
1kV
Conducted disturbance
EN 61000-4-6 0.15-80MHz
10V
Criterion A: The PISA protection module shows normal operation behavior within the defined limits.
*)… on coupling plane
Outputs
OFF
8kV
8kV
10V/m
2kV
2kV
1kV
500V
1kV
500V
1kV
1kV
10V
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
EMC Emissions
Generic standards: EN 61000-6-3, EN 61000-6-4
Conducted emission
input and output lines**)
IEC/ CISPR 16-1-2, IEC/ CISPR 16-2-1
Radiated emission
EN 55011, EN 55022
**) provided that the supplying power source fulfills these requirements too
limits for DC power ports according
to EN 61000-6-3 fulfilled
Class B
May 2014 / Rev. 1.7 DS-PISA11.CLASS2 - data sheet -
All parameters are specified at 24Vdc input, 25°C ambient temperature and a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278-0 Germany
14/19