PISA11.CLASS2 Datasheet, PDF (1/19 Pages) PULS GmbH – PROTECTION MODULE 24V, 4 OUTPUTS
PISA11-Series
PISA11.CLASS2
PROTECTION MODULE 24V, 4 OUTPUTS
PROTECTION MODULE
ƒ One Input and Four Current Controlled Outputs
ƒ NEC Class 2 Compliant Outputs
ƒ Ensures Sufficient Supply Voltage for Critical Loads
even in the Event of an Fault
ƒ Protects Small Cable Sizes against Overload
ƒ Hassle-free Turn-on of Loads with Large Input
Capacitors
ƒ Wide Temperature Range between -25°C and +70°C
ƒ On/Off Function of Outputs
ƒ Compact Design, Width only 45mm
ƒ Remote Monitoring and Control Functions
ƒ 3 Year Warranty
GENERAL DESCRIPTION
This protection module fulfills two basic functions. First it
distributes the current of a large (non NEC Class 2) power
source to four NEC CLASS 2 output channels and therefore
allows for a simpler wiring method and easier approval
process of the entire machine. The second function is to
permit only so much current on the outputs that the input
voltage of this unit (which corresponds to the output
voltage of the power supply) does not fall below 21V.
This ensures a safe and an uninterrupted supply voltage for
sensitive equipments, such as PLCs, controls or sensors, when
they
are
connected
directly to the
same power
DC 24V
Power
Supply
PISA Protection Module
A1
Non NEC CLASS 2 Load
NEC CLASS 2 Circuit 1
supply as the
A2
NEC CLASS 2 Circuit 2
PISA module.
A3
NEC CLASS 2 Circuit 3
Less critical
A4
NEC CLASS 2 Circuit 4
loads that are
Safeguard
not affected to short voltage interruptions or that could
even be the cause of a fault on the 24V power supply are
connected to one of the four NEC CLASS 2 output channels
of the PISA module.
ORDER NUMBERS
SHORT-FORM DATA
Input voltage
DC 24V
Input voltage
18 - 30V
range
Input current
typ. 43mA
At no load
Number of outputs 4
Output currents 4x 3.7A at 24V
4x 3.2A at 28V
Input voltage
typ. 21.4V
protection levels
Temperature range -25°C to +70°C Operational
-40°C to +85°C Storage
Type of current
Active current limitation followed
limitation
by a shutdown
Dimensions
45x75x91mm *) WxHxD
*) Add 13mm in depth for signal connector.
MARKINGS
Protection
module
PISA11.CLASS2
4x NEC CLASS 2
outputs
IND. CONT. EQ.
UL 508
UL 60950-1
IEC 60950-1
NEC CLASS 2
UL 2367
EMC, LVD
ATEX
II 3G EX nA nC IIC T4
Class I Div 2
May 2014 / Rev. 1.7 DS-PISA11.CLASS2 - data sheet -