English
Language : 

PISA11.CLASS2 Datasheet, PDF (13/19 Pages) PULS GmbH – PROTECTION MODULE 24V, 4 OUTPUTS
PISA11-Series
PISA11.CLASS2
PROTECTION MODULE 24V, 4 OUTPUTS
16. TERMINALS AND WIRING
All terminals are easy to access when mounted on the panel.
Input, outputs and signal terminals are separated from each other to help in error-free wiring.
Type
Solid wire
Stranded wire
AWG (American Wire Gauge)
Wire stripping length
Screwdriver
Recommended tightening torque
Input and Output
screw terminals
0.2-6mm2
0.2-4mm2
24-10 AWG
7mm / 0.28inch
3.5mm slotted or
Pozidrive No 2
0.8Nm, 7lbs.in
Signals
plug connector
0.2-1.5mm2
0.2-1.5mm2
24-16 AWG
6mm / 0.24inch
2.5mm slotted
0.35Nm, 3lbs.in
Instructions:
a) Use NEC Class 2 rated wires for the output
b) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and minimum
75°C for ambient up to 60°C and minimum
90°C for ambient up to 70°C.
c) Follow national installation codes and installation regulations!
d) Ensure that all strands of a stranded wire enter the terminal connection!
e) Screws of unused terminal compartments should be securely tightened.
f) Ferrules are allowed.
May 2014 / Rev. 1.7 DS-PISA11.CLASS2 - data sheet -
All parameters are specified at 24Vdc input, 25°C ambient temperature and a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278-0 Germany
13/19