11. FUNCTIONAL DIAGRAM
+
Input
-
-
Input
Status
Reset,
ON/OFF
Reset, 12
ON/OFF 11
Outputs- 13
OK
Contact 14
15
Sync.
16
Fig. 11-1 Functional diagram
Safeguard
for Minimum
Input Voltage
I Sense
NEC-CLASS-2
Controller
Current
Limiter &
Shut-down
Manager
Redundant
Emergency
Switch
I Sense
I Sense
I Sense
(+)
Reset,
(-)
ON/OFF
Output
OK
Synchro-
nization
I Sense
Output
Current
Monitor
Failure
+ Output 1
Failure
+ Output 2
Failure
+ Output 3
Failure
+ Output 4
12. BACK-FEEDING LOADS
Loads such as decelerating motors and inductors can feed voltage back to the PISA11 protection module. This feature
is also called return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force).
The protection module is resistant and does not show malfunctioning when a load feeds back voltage up to 30Vdc to
the protection module. It does not matter whether the protection module is on or off.
The protection module has no capability to absorb energy. Internal diodes (integrated body diodes of the Mosfets)
directs the voltage and energy to the power supply, which is connected on the input side of the protection module.
The power supply defines the amount of energy which can be absorbed.
May 2014 / Rev. 1.7 DS-PISA11.CLASS2 - data sheet -
All parameters are specified at 24Vdc input, 25°C ambient temperature and a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278-0 Germany
10/19