S8VS Datasheet, PDF (8/24 Pages) Omron Electronics LLC – Switch mode Power Supply (Visible and Slim New Din Rail Power Supply)
I Undervoltage Alarm Indication
This indicator lights when the output voltage is insufficient.
Operation
Mode
Undervoltage
alarm
Output
current
Undervoltage occurs.
*
Output voltage lower limit
* This indicator alternately
displays alarm ( )
and the output voltage
lower limit.
Peak-hold
current
I Maintenance Forecast
Displays when the maintenance forecast has reached the set value.
Operation
Mode
Maintenance
forecast
monitor
Output
voltage
The maintenance forecast
has reached the set value.
*
Remaining time
until replacement
* This indicator alternately
displays alarm ( )
and the maintenance
time until replacement.
Output
current
Maintenance
forecast
monitor
Note: The display changes to the output voltage display when the
voltage is restored to the set value or higher.
I Multiple Alarms
When two or more different alarms occur at the same time
Operation Mode
Undervoltage
alarm
*
Maintenance
forecast monitor
The indication shifts
alternately in the direction
of the arrow every 2 s.
*
* When undervoltage alarm is indicated: Press
output load indication
When the maintenance forecast monitor or overheat alarm is indicated:
Press
undervoltage alarm indication
Peak-hold
current
I Indication and Output
When the product is purchased, “ful” will be indicated. As electro-
lytic capacitors deteriorate, indication changes to “hlf”. After the
remaining time to maintenance is reduced to two years, indication
automatically changes to a value, which decreases from “1.5” to “1.0”
to “0.5” to “0” (year) as the running hours increase.
If the maintenance forecast monitor setting is set to a value larger
than two years, value indication automatically begins after the
remaining time to maintenance is reduced to the set years.
If the remaining time becomes smaller than setting L (which can be
set arbitrarily between 0 and 5.0 years), an alarm (a02) and the
remaining time are indicated alternately.
With the S8VS-09024A, an output is given to an external device from
a transistor ((12) Yrs) to notify of the replacement timing, together
with indication. (The output is turned off after the replacement timing
is reached; with no continuity across (12) and (13).)
In the case that the
remaining time is reduced
to smaller than 0.5 year
and an alarm is issued.
Note: 1. The remaining time to maintenance is based on continuous
operation, not including the time when the power supply is
turned off, and so may take longer to reach than the actual
time indicated.
2. Until the power supply has been turned for about one month
in total, indication is fixed at “ful” to estimate the extent of
deterioration, while the output remains turned on (with con-
tinuity across (12) and (13)).