English
Language : 

S8VS Datasheet, PDF (4/24 Pages) Omron Electronics LLC – Switch mode Power Supply (Visible and Slim New Din Rail Power Supply)
I Installation
60-W Model
S8VS-06024
1
2
4
5
3
90-W Model
S8VS-09024
1
2
S8VS-06024@
1
2
6
7
8
4
5
3
S8VS-09024@
1
2
6
7
10
8
9
4
5
3
No.
Name
1 AC Input terminals
(L), (N)
2 Ground terminals
(GR)
3 DC Output terminals
(−V), (+V)
4 Output indicator
(DC ON: Green)
5 Output voltage
adjuster (V.ADJ)
6 Main display
(See note 2.)
7 Operation
V
indicator
(See note 2.)
A
Apk
Yrs
Kh
Function
Connect the input lines to these
terminals. (See note 1.)
Connect the ground line to this terminal.
Connect the load lines to these
terminals.
Lights while a direct current (DC) output
is ON.
Use to adjust the voltage.
Indicates the measurement or set value.
Lights up when the output voltage is
indicated. Blinks during setup of
undervoltage alarm value.
Lights up during indication of output current.
Lights up during indication of peak hold current.
Lights up during indication of maintenance
forecast monitor. Blinks during setup of
maintenance forecast monitor setting.
(S8VS-0…024A)
Lights up during indication of total run
time monitor. Blinks during setup of total
run time monitor. (S8VS-0@024B)
4
5
11 13
12 3
No.
Name
Function
8 Mode Key (See note 2.)
Use the Mode Key to change the
indicated parameter or reset the
peak hold current value.
9 Up Key (See note 3.)
Use the Up Key to change to the
setting mode or to increase the set
value.
10 Down Key (See note 3.)
Use the Down Key to change to
the setting mode or to decrease
the set value.
11 Alarm Undervoltage alarm Outputs when a drop in the
output output terminal (DC output voltage is detected.
terminal LOW) (See note 3.) (at voltage drop: OFF)
12
Maintenance forecast Outputs when the maintenance
monitor terminal (Yrs) forecast has reached the set
(S8VS-09024A)
value.
Total run time monitor
output terminal (Kh)
(S8VS-09024B)
(See note 3.)
13
Common terminal Terminal (emitter) shared for
for alarm output
alarm outputs (11) and (12).
(See note 3.)
Note: 1. The fuse is located on the (L) side.
2. S8VS-@@@24@ only.
3. S8VS-09024@ Model only.
L-58