English
Language : 

S8VS Datasheet, PDF (5/24 Pages) Omron Electronics LLC – Switch mode Power Supply (Visible and Slim New Din Rail Power Supply)
Engineering Data
I Derating Curve
120
100
80
60
40
20
0
−20 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (˚C)
Installation
Upper
Upper
Standard mounting
Face-up mounting
Note: 1. Use standard mounting only. Using any other mounting
method will prevent proper heat dissipation and may result
in deterioration or damage of internal elements. Or, the re-
maining service life notice function cannot work properly.
2. If there is a derating problem, use forced air-cooling. The
ambient temperature is specified for a point 50 mm below
the power supply.
I Overload Protection
The Power Supply is provided with an overload protection function
that protects the load and the power supply from possible damage by
overcurrent. When the output current rises above 105% min. of the
rated current, the protection function is triggered, decreasing the out-
put voltage. When the output current falls within the rated range, the
overload protection function is automatically cleared.
I Overvoltage Protection
The Power Supply is provided with an overvoltage protection function
that protects the load and the Power Supply from possible damage
by overvoltage. When an excessive voltage is output, the output volt-
age is shut OFF. Reset the Power Supply by turning it OFF for at
least three minutes and then turning it back ON again.
+15%
Rated output
voltage
−10%
Overvoltage protection
operating
Variable range
0V
Note: Do not turn ON the power again until the cause of the overvolt-
age has been removed.
I Inrush Current, Start Up Time,
Hold Time
Input ON
AC input
voltage
Input OFF
AC input
current
Output
voltage
Inrush current on input application
90%
Start up time (1,000 ms max.)
96.5%
Hold time (20 ms min.)
Intermittent operation
0
50
100
Output current (%)
Note: Do not allow the short-circuited or overcurrent state to continue
for more than 20 s, otherwise internal elements may deteriorate
or be destroyed.
Switch mode Power Supply S8VS
L-59