I Ratings/Characteristics
Power ratings
60 W
90 W
Item
Type Standard
Maintenance Total run time
forecast monitor monitor
Standard
Maintenance Total run time
forecast monitor monitor
Efficiency (typical)
78% min.
80% min.
Input
Voltage
100 to 240 VAC (85 to 264 VAC)
Frequency
50/60 Hz (47 to 450 Hz)
Current
100 V input 1.7 A
2.3 A
200 V input 1.0 A
1.4 A
Power factor correction
Conforms to EN61000-3-2 A-14
Leakage
current
100 V input 0.5 mA max.
200 V input 1.0 mA max.
Inrush current 100 V input 25 A max.
(See note 1.) 200 V input 50 A max.
Output Voltage adjustment range −10% to 15% (with V.ADJ)
Ripple
2.0% (p-p) max. (at rated input/output voltage)
Input variation influence 0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation influence
(rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Start up time (See note 1.) 1,000 ms max.
500 ms max. 1,000 ms max.
500 ms max.
(at rated input/output voltage)
(at rated input/output voltage)
Hold time (See note 1.)
20 ms min. (at rated input/output voltage)
Additional Overload protection (See note 1.) 105% to 160% of rated load current, inverted L drop, intermittent, automatic reset
function Overvoltage protection (See note 1.) Yes
Output voltage indication (See note 2.) No
Yes (selectable) (See note 3.) No
Yes (selectable) (See note 3.)
Output load indication (See note 2.) No
Yes (selectable) (See note 4.) No
Yes (selectable) (See note 4.)
Peak-hold load indication (See note 2.) No
Yes (selectable) (See note 5.) No
Yes (selectable) (See note 5.)
Maintenance forecast monitor No
Yes (select- No
No
Yes
No
indication (See note 2.)
able)
(selectable)
Maintenance forecast
No
monitor output
Yes (open collector No
output), 30 VDC max.,
50 mA max.
Total run time monitor
No
indication (See note 2.)
Yes
No
(selectable)
Yes
(selectable)
Total run time monitor
No
output
Yes (open collector
output), 30 VDC max.,
50 mA max.
Undervoltage alarm
No
indication (See note 2.)
Yes (selectable)
No
Yes (selectable)
Undervoltage alarm output No
terminals
Yes (open collector output),
30 VDC max., 50 mA max.
Parallel operation
No
Series operation
Yes (with external diode)
Other
Ambient temperature
Operating: Refer to the derating curve in Engineering Data. (with no icing or condensation) Storage: −25 to 65°C
Ambient humidity
Operating: 25% to 85%; Storage: 25% to 90%
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and GR terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and GR terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance
100 MΩ min. (between all outputs/ alarm outputs and all inputs/ GR terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator
Yes (color: green)
Electromagnetic interference Conforms to FCC Class A, EN50081-2
EMI
Conforms to EN50081-2
Approved standards
UL: UL508 (Listing; Class 2: Per UL1310), UL60950
UL: UL508 (Listing), UL60950
cUL: CSA C22.2 No.14, No.60950 (Class 2)
cUL: CSA C22.2 No.14, No.60950
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0806) EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0806)
Weight
330 g max.
490 g max.
Note: 1. Refer to the Engineering Data section on page 59 for details.
2. Displayed on 7-segment LED.
3. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (±1 digit for output voltage value)
4. Resolution of output load indication: 0.1 A, Precision of output load indication: ±5% (±1 digit for output load value)
5. Resolution of Peak-hold load indication: 0.1 A, Precision of Peak-hold load indication: ±5% (±1 digit for output load value), width of Peak-
hold load indication: 10 ms
L-56