English
Language : 

S8VS Datasheet, PDF (6/24 Pages) Omron Electronics LLC – Switch mode Power Supply (Visible and Slim New Din Rail Power Supply)
I Undervoltage Alarm Function (Indication and Output)
When output voltage drop is detected, an alarm (a01) and lowest
output voltage value are indicated alternately. The preset value of
detection voltage can be changed in the setting mode.
(S8VS-06024@: The value of detection voltage is fixed at 20V)
Further, the alarm is output from the transistor ((11) DC LOW) to an
external device with the S8VS-09024A/B.
(Upon output voltage alarm: OFF; with no continuity across (11) and
(13))
:
In the case that the
output voltage drops
below the set value (19V)
and an alarm is issued
Note: 1. Operation begins after about two seconds since the AC
power is supplied.
2. The alarm is not indicated in the setting mode.
3. Press the ((8) Mode Key) after the output voltage is re-
stored, to reset alarm indication.
4. The undervoltage alarm function monitors the output termi-
nal voltage of the power supply unit. To check the voltage
accurately, measure the voltage at the load end.
AC input
Output
voltage
Detection value
of Undervoltage
alarm
Undervoltage
output
Main display
Operation
mode
Lowest value of
output voltage
Voltage indication
Note: Operation begins after about three seconds since the AC pow-
er is supplied.
Engineering Data (S8VS-@@@24@ Only)
I Mode Change
Power-ON
Model indication
Operation mode
Press and hold
Up or Down Key for
three seconds or more.
Key Press and hold for
three seconds or more.
Or no key operation for 30 seconds or more.
Setting mode
Note: No setting mode is provided for the S8VS-06024@.
I Operation Mode
Various states of the power supply unit are indicated.
Output voltage
Output current
Peak hold current
Maintenance forecast monitor
(S8VS-@@@24A)
or total run time monitor
(S8VS-@@@24B)
Note: The output voltage will be displayed when the power supply is
first turned on after it is received from the factory. Thereafter,
the output voltage will be indicated in the same display when
shutting down.
L-60