S8JXG05012CD Datasheet, PDF (7/59 Pages) Omron Electronics LLC – Switch Mode Power Supply
S8JX
Input specification 100/200 V switchable
100 to 240 V input
Item
Power ratings *1
150 W at 5 V
150 W at 12 V
150 W at 24 or 48 V
5-V Models
78% min.
---
---
Efficiency
12-V Models
24-V Models
---
79% min.
---
---
---
86% min.
48-V Models
---
---
85% min.
Voltage *2
Switchable between 100 to
120 VAC (allowable range:
85 to 132 VAC) and 200 to
240 VAC (allowable range:
170 to 264 VAC).
100 to 240 VAC (allowable range: 85 to 264 VAC)
80 to 370 VDC *9
Frequency *2
50/60 Hz (47 to 450 Hz)
Input
Current *3
Power factor
100 V input
200 V input
3.5 A max.
2.1 A max.
3.6 A max.
2.2 A max.
---
3.5 A max.
2.1 A max.
Harmonic current emissions
---
Leakage current *3
100 V input
200 V input
0.5 mA max.
1 mA max.
Inrush current (for a 100 V input
cold start at 25°C) *3 200 V input
20 A max.
40 A max.
Noise filter
Yes
Voltage adjustment range *5
−10% to 15% (with V. ADJ) (48-V models: ±10%)
Ripple *3
2% (p-p) max.
Input variation influence
0.4% max. (with AC input voltage)
Output *4 Load variation influence
0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence
0.05%/°C max. (at rated input and output)
Startup time
500 ms max. (up to 90% of output voltage at rated input and output)
Hold time *3
20 ms min.
Overload protection *6
105% to 175% of rated load
current, voltage drop,
105% to 175% of rated load current, voltage drop,
automatic reset
intermittent, automatic reset
Additional Overvoltage protection *7
Yes
functions Overheat protection
No
Parallel operation
No
Series operation
Yes (For up to two Power Supplies; external diodes required.)
Protective circuit operation indicator
No
Ambient operating temperature
Refer to the derating curve in Engineering Data on page 16 (with no icing or
condensation).
Storage temperature
−25 to 65°C (with no icing or condensation)
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Insulation resistance
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator
Yes (Color: Green)
EMI
Other
Conducted Emissions
Radiated Emissions
Electrostatic Discharge
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9
Conforms to EN 55011 Group 1 Class A *9
Conforms to EN61000-4-2
Radiated Electromagnetic Field Conforms to EN61000-4-3
EMS
Electrical Fast Transient/Burst Conforms to EN61000-4-4
Surge
Conforms to EN61000-4-5
Conducted Disturbance
Conforms to EN61000-4-6
Voltage Dips/Short Interruptions Conforms to EN61000-4-11
UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition)
Approved standards *9
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160), Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI
---
SEMI F47-0200 (200-VAC input)
Weight *8
800 g max.
700 g max.
600 g max.
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 19.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 19.
*7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON.
*8. The weight indicated is for Front-mounting, Open-frame Power Supply.
*9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
7