Y92S-27 Datasheet, PDF (44/61 Pages) Omron Electronics LLC – DIN 48 x 48-mm Multifunctional Timer Series
H3CR-H
■ Ratings
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC,
100 to 125 VDC
Operating voltage range
85% to 110% of rated supply voltage
No-voltage input (See note 3.)
ON-impedance: 1 kΩ max.
ON residual voltage: 1 V max.
OFF impedance: 500 kΩ min.
Power consumption
100 to 120 VAC: approx. 0.23 VA (0.22 W) at 120 VAC
200 to 240 VAC: approx. 0.35 VA (0.3 W) at 240 VAC
24 VAC/DC:
approx. 0.17 VA (0.15 W) at 24 VAC
approx. 1.0 W at 24 VDC
48 VDC:
approx. 0.18 W at 48 VDC
100 to 125 VDC: approx. 0.5 W at 125 VDC
Control outputs
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
3. For contact input, use contacts which can adequately switch 1 mA at 5 V.
■ Characteristics
Accuracy of operating
time
Setting error
Operation start voltage
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand
voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
EMC
Case color
Degree of protection
Weight
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
±5% FS ±50 ms max.
30% max. of rated voltage
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
±1% FS max. (±1% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
100 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
5 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC;
1 kV for 24 VAC/DC, 48 VDC
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120 VAC, 200 to
240 VAC, 100 to 125 VDC;
1.5 kV for 24 VAC/DC, 48 VDC
±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator
(pulse width: 100 ns/1 μs, 1-ns rise); ±1 kV (between power terminals) for 48 VDC
Malfunction: 8 kV, Destruction:15 kV
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Destruction: 980 m/s2 three times each in six directions
Malfunction: 98 m/s2 three times each in six directions
Operating: −10°C to 55°C (with no icing),
Storage: −25°C to 65°C (with no icing)
Operating: 35% to 85%
Mechanical: 10 million operations min. (under no load at 1,200 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h) (See note)
(EMI)
EN61812-1
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
(EMS)
EN61812-1
Immunity ESD:
IEC61000-4-2
Immunity RF-interferenc:
IEC61000-4-3
Immunity Burst:
IEC61000-4-4
Immunity Surge:
IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Light Gray (Munsell 5Y7/1)
IP40 (panel surface)
Approx. 120 g
Note: Refer to the Life-test Curve(Reference).
44