English
Language : 

Y92S-27 Datasheet, PDF (36/61 Pages) Omron Electronics LLC – DIN 48 x 48-mm Multifunctional Timer Series
Specifications
H3CR-G
■ General
Item
Functions
Pin type
Operating/Reset method
Output type
Mounting method
Approved standards
H3CR-G8L
H3CR-G8EL
Star-delta timer
Star-delta timer with instantaneous output
8-pin
Time-limit operation/Self-reset
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Instantaneous: SPST-NO
DIN track mounting, surface mounting, and flush mounting
UL508, CSA C22.2 No.14, NK, Lloyds, CCC
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
Note: For details, refer to your OMRON website.
■ Time Ranges
Time unit
Scale number (max.)
6
Set time range 0.5 to 6 s
12
1 to 12 s
60
5 to 60 s
120
10 to 120 s
Star operation time ranges
Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s, or 1.0 s
■ Ratings
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)
Operating voltage range
85% to 110% of rated supply voltage
Power reset
Minimum power-opening time: 0.5 s
Power consumption
100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC
Control outputs
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy
Note: 1. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
2. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
36