Event C: The Status register bit 1 (RCRIT) is reset by a read of the Status register (in
the interrupt mode).
7.9.3 Fault Queue
To suppress erroneous ALERT or T_CRIT triggering, the SA56004X implements a Fault
Queue for both local and remote channel. The Fault Queue insures a temperature
measurement is genuinely beyond a HIGH, LOW or T_CRIT setpoint by not triggering
until three consecutive out-of-limit measurements have been made. The fault queue
defaults OFF upon POR and may be activated by setting bit 0 in the Configuration register
(address 09h) to logic 1.
remote temperature
RCS
RCS − TH
remote HIGH setpoint
remote LOW setpoint
ALERT output
SA56004X_5
Product data sheet
T_CRIT output
events A
B
C
DEF G
H
I
002aad218
Fig 8.
Remark: All events indicate the completion of a conversion.
Fault queue remote HIGH and LOW and T_CRIT, T_CRIT hysteresis setpoint
response (comparator mode)
Event A: The remote temperature has exceeded the Remote HIGH setpoint.
Event B: Three consecutive over limit measurements have been made exceeding the
Remote HIGH setpoint; the ALERT output is activated (goes LOW). By now, the remote
temp has exceeded the Remote T_CRIT setpoint (RCS).
Event C: Three consecutive over limit measurements have been made exceeding RCS;
the T_CRIT output is activated (goes LOW).
Event D: The remote temperature falls below the RCS − TH setpoint.
Event E: The ALERT output is de-activated (goes HIGH) after a below_high_limit
temperature measurement is completed.