7.1.2 Device Status Parameter in the
Transducer Block
The following table lists the conditions indicated in the
Device Status parameter. It also shows the affect the condition
has on PV status, Sub-Status and Limit, XD ERROR and
BLOCK ALARM are not affected by these conditions directly.
Type
Mode
Mode
Mode
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Device Status
Label
Bit #
Value
PV Status
Quality
OK
15 0x00008000 Good
User Access 7 0x00000080 Bad
Factory Access 5 0x00000020 Bad
Default Params 28 0x10000000 Bad
No End of Ramp 27 0x08000000 Bad
Lvl<Probe Length 23 0x00800000 Bad
No Fiducial 21 0x00200000 Bad
Safety Zone FLT 20 0x00100000 Bad
No Signal
19 0x00080000 Bad
EOP<Probe Length 18 0x00040000 Bad
EOP High
17 0x00020000 Bad
High Volume Fit 16 0x00010000 Bad
Hi Temperature 11 0x00000800 No Effect
Lo Temperature 10 0x00000400 No Effect
Default Cal
9 0x00000200 No Effect
Initializing
4 0x00000010 No Effect
May be Flooded 3 0x00000008 No Effect
Dry Probe
2 0x00000004 No Effect
Weak Signal
1 0x00000002 No Effect
No Steam Target 6 0x00000040 No Effect
PV Sub Status
Non-Specific
OOS
OOS
Configuration Error
Device Failure
Sensor Failure
Device Failure
Non-Specific
Sensor Failure
Sensor Failure
Configuration Error
Configuration Error
No Effect
No Effect
No Effect
Initial Value
No Effect
No Effect
No Effect
No Effect
Limit
Not Limited
Not Limited
Not Limited
Not Limited
Constant Limited
Constant Limited
Constant Limited
Not Limited
Constant Limited
Constant Limited
Not Limited
High Limited
No Effect
No Effect
No Effect
Constant Limited
High Limited
Low Limited
No Effect
No Effect
The first three conditions are Type Mode. If everything is
running normally and there are no Faults or Warnings, then
the device indicates it is “OK” an the local display and in
Device Status. If a password is entered through the local dis-
play, the Transducer Block is taken Out of Service if it is not
already and the User Access or Factory Access will be indi-
cated in Device Status. This will indicate to the operator
that an attempt is being made to modify a parameter value.
No indication is given on the Fieldbus network if someone
is only viewing parameters on the local display.
The next set of conditions is device faults. The device will
most likely not be able to measure level correctly if one or
more of these conditions occur. The condition will be indi-
cated in Device Status and will affect PV Status, Sub-Status
and Limit as indicated.
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus