100%
Probe Length
0%
Offset
Default Scaling
28
4.4.2 Firmware Version
The last parameter in the TRANSDUCER block gives the
firmware version of the transmitter.
FIRMWARE_VERSION: displays the version of the
firmware.
NOTE: The user should compare the DD file and revision number of the
device with the HOST system to ensure they are at the same
revision level.
Refer to the table on page 6.
4.5 Analog Input Block
The ANALOG INPUT (AI) block takes the Eclipse Model
705 input data, selected by channel number, and makes it
available to other function blocks at its output:
Channel Process Value
1 Level
2 Volume
3 Interface
4 Interface Volume
4.5.1 AI Block Parameters
PV: Either the primary analog value for use in executing the
function, or a process value associated with it.
OUT: The primary analog value calculated as a result of
executing the function block.
SIMULATE: Allows the transducer analog input or output
to the block to be manually supplied when simulate is
enabled. When simulate is disabled, the simulate value and
status track the actual value and status
XD_SCALE: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point used with the value obtained from the transducer for
a specified channel.
OUT_SCALE: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point to be used in displaying the OUT parameter.
GRANT_DENY: Options for controlling access of host
computers and local control panels to operating, tuning,
and alarm parameters of the block.
IO_OPTS: Option which the user may select to alter input
and output block processing.
STATUS_OPTS: Options which the user may select in the
block processing of status.
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus™