Language : 

705-5100-121 Datasheet, PDF (10/56 Pages) Magnetrol International, Inc. – GuidedWave Radar Level Transmitter
2 Probe Mount
1 Probe Model
6
Dielectric
of Medium
Enter
Down
Up
2.4 QuickStart Configuration
The Eclipse transmitter comes partially configured from
the factory but can be reconfigured in the shop (disregard
fault message due to unattached probe). The minimum
configuration instructions required in the field follow.
1. Power up the transmitter.
The display changes every 5 seconds alternating between
showing the Status, Level and Analog Input Block values.
2. Remove the cover of the lower electronic compartment.
3. Use the Up or Down Arrow ( ) keys to move from one
step of the configuration program to the next step.
4. Press the Enter Arrow ( ) key. The last
character in the first line of the display
changes to an exclamation point (!).
PrbModel
xxx
5. Use the Up or Down Arrow ( ) keys to increase or
decrease the value in the display or to scroll through the
choices.
6. Press the Enter Arrow ( ) key to accept a value and move
to the next step of the configuration program (the default
password is 1).
7. After entering the last value, allow 10 seconds before
removing power from the transmitter.
The following configuration entries are the minimum required for
configuration (the default password is 1 from the LCD/keypad).
4
Probe Length
Level Offset 5
x
PrbModel
(select)
y
PrbMount
(select)
z
MeasType
(select)
Probe Ln
{ xxx.x
|
LvlOfst
xxx.x
Dielctrc
} (select)
Select the Probe Model to be used
Model 705: 7xA-x, 7xB-x, 7xD-x, 7xE-x, 7xF-F, 7xF-P,
7xF-4, 7xF-x, 7xJ-x, 7xK-x, 7xP-x, 7xR-x, 7xS-x,
7xT-x, 7x1-x, 7x2-x, 7x5-x, 7x7-x
Select the type of Probe Mounting to vessel (NPT, BSP, or
flange).
Select from Level Only, Level and Volume, Interface Level
or Interface Level and Volume.
Enter the exact Probe Length as printed on the probe
nameplate.
Enter the Level Offset value. Refer to Section 4.3.4 for
further information. (The unit is shipped from the factory
with offset = 0; i.e., all measurements are referenced to
the bottom of the probe).
Enter the Dielectric range for the material to be measured.
10
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus™