4.6.1 PID Block Parameters (cont.)
DV_LO_LIM: The setting for the alarm limit used to
detect the deviation low alarm condition.
DV_LO_PRI: The priority of the deviation low alarm.
FF_GAIN: The feedforward gain value.
FF_SCALE: The high and low scale values associated with
FF_VAL.
FF_VAL: The feedforward control input value and status.
GAIN: The proportional gain value. This value cannot
equal zero.
GRANT_DENY: Options for controlling access of host
computers to alarm parameters of the block.
HI_ALM: The HI alarm data
HI_HI_ALM: The HI HI alarm data
HI_HI_LIM: The setting for the alarm limit used to detect
the HI HI alarm condition.
HI_HI_PRI: The priority of the HI HI Alarm.
HI_LIM: The setting for the alarm limit used to detect the
HI alarm condition.
HI_PRI: The priority of the HI alarm.
IN: The connection for the PV input from another block.
LO_ALM: The LO alarm data.
LO_LIM: The setting for the alarm limit used t detect the
LO alarm condition.
LO_LO_ALM: The LO LO alarm data.
LO_LO_PRI: The priority of the LO LO alarm.
LO_PRI: The priority of the LO alarm.
MATH_FORM: Selects equation form (series or standard).
MODE_BLK: The actual, target, permitted, and normal
modes of the block.
OUT: The block input value and status.
OUT_HI_LIM: The maximum output value allowed.
OUT_LO_LIM: The minimum output value allowed.
OUT_SCALE: The high and low scale values associated
with OUT.
PV: The process variable use in block execution.
PV_FTIME: The time constant of the first order PV filter.
PV_SCALE: The high and low scale values associated with PV.
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus™