705-5100-110 Datasheet, PDF (25/68 Pages) Magnetrol International, Inc. – Enhanced Model 705
2.6.5.2 Measurement Type: Level and Volume (Loop Control = Volume)
Display
22
SZ Fault
(select)
Action
Comment
Select loop current behavior Safety Zone is a user-defined area just below the Blocking
when level is sensed in safety Distance. Enable Fault if necessary to ensure safe, reliable high-
zone
level readings in critical applications. Choices are None, 3.6 mA,
22 mA, Latch 3.6 or Latch 22. If Latch 3.6 or Latch 22 is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#23)
Enter distance below
Enter a distance value that develops a safety zone just below the
23
SZHeight
xx.x lu
BlockDis where SZ Fault will Blocking Distance. Here the unit will report a Safety Zone Fault
be asserted
(#21) if the level rises into this area.
24
Press Enter to clear a
SZ Alarm Reset
latched Safety Zone alarm
Clear a latched Safety Zone alarm
Select the type of threshold Unit default CFD. Only select Fixed in application with low
25
Threshld
(select)
dielectric material over higher dielectric material and unit is read-
ing incorrect level. Example: Oil over water. (Adjustment of Trim
Level may be necessary when threshold is changed)
26
Poll Adr
xx
Enter HART polling address Select a HART poll address (0–15). Enter 0 for a single
number (0-15)
transmitter installation
27
Trim Lvl
xx.x lu
Enter value to adjust Level
reading
-10.0 inches <= Lvl Trim <= +10.0 inches
(Requires superuser password)
28
Trim 4
xxxx
Fine tune the 4 mA point
Adjust setting to output exactly 4.0 mA on current meter
29
Trim 20
xxxx
Fine tune the 20 mA point Adjust setting to output exactly 20.0 mA on current meter
30
Loop Tst
xx.x mA
Enter a mA Output value
Set mA output to any given value to perform loop test
31
LvlTicks
xxxx
Diagnostic Display
Time of flight from fiducial to level signal
32
New Pass
xxx
Enter new password (0-255) Displays encrypted value of present password
33
Language
(select)
Select from English, Spanish, Language choice for LCD display
French, German
34
Mdl705HT
Ver3.0a0
Transmitter display
Product identification Firmware version
35
DispFact
(select)
Select Yes to display factory Allows for viewing the factory parameters
parameter menus
36
History
Press Enter to view history Diagnostic Display
(current status) of recent exceptions
37
HF cable
(select)
Superuser Parameter
Select from 3-foot or 12-foot remote
38
Run Time
39
Press Enter and select yes Similar to SZ Alarm Reset
History Reset
to clear history
40
FidTicks
xxxx
Diagnostic Display
Time of flight from start of ramp to fiducial
41
Fid Type
(select)
Superuser Password
Select from positive or negative
(Selection only allowed for some probes)
42
Fid Spread
57-600 Eclipse Guided Wave Radar Transmitter
25