2.4.3 Program Path 4 — Multi-Point
The following procedure must be follower if MULT
(multi-point) has been selected in Program Path 1 CNFG
(configuration). Probe calibration, Program Path 2, must
RUN
also be accomplished for the Multi-Point program to
XXXX
operate. These two procedures, Multi-Point and Probe
Calibration, can be done in any order.
ENT
CNTL
NORM
NOTE: Use the same unit of measure that was used in Probe
Calibration. Be consistent throughout the program.
ENT
LEAD
ENT
FALT
DNRG
IGNR
FALT
SET
LVLO
XXXX
ENT
ENT
LVHI
XXXX
ENT
Press ENT ENT to read DISP. Press the DOWN arrow
key to display MODE.
STEP 1: DISP (Display)
1. Press ENT ENT to read DISP. The display will read the
actual process level, based on the unit of measure that was
used in Probe Calibration (PRLO/PRHI).
2. Press the DOWN arrow key to display MODE.
STEP 2: MODE (Mode)
KILL
ENT
TDLO
XXXX
ENT
TDHI
XXXX
ENT
ENT
LLFS
ENT
HLFS
1. MODE refers to the configuration of both the control
mode and the fault mode. Press ENT ENT to display CNTL
(control). Control allows for selection of normal or
lead-lag pump control.
2. If this is the desired condition, press ENT ENT .
3. The next level of the menu will be displayed; the selection
of normal or lead-lag pump control. Choosing NORM will
allow normal operation of the relays. If lead-lag pump
sequencing is desired, press the DOWN arrow key to
display LEAD.
NOTE: Selection of LEAD (lead-lag) affects relays 2 and 3 only and
does not apply to Model 822. LEAD must NOT be selected for
Model 822.
4. Once the proper choice is displayed, press ENT ENT to
display FALT.
5. Press ENT ENT to display DNRG (de-energize). In this
position, all control relays will de-energize (go to a fail-safe
state) when a fault is diagnosed.
6. Use the UP or DOWN arrow keys to toggle
between DNRG (de-energize) or IGNR (ignore). If IGNR is
chosen, all control relays will continue operating when a
fault is diagnosed.
7. Press ENT ENT to store the appropriate choice. The unit
reads RLY1.
50-621 Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches