822-1002-C01 Datasheet, PDF (22/40 Pages) Magnetrol International, Inc. – Kotron® Sentinel Models 822, 832 and 842
Probe
high
Probe low
Figure 14
3. Press the DOWN arrow key to get to MODE. Press
ENT ENT .
4. Scroll to SING. Press ENT ENT . Unit reads NOT READY.
You are now in the Single Point Mode.
5. Return to CNFG and repeat the above procedure now
choose MULT from the MODE menu. Press ENT ENT . Unit
reads MAGNETROL INTL M M M….
6. All of the original data has now been cleared.
7. Begin Probe Calibration procedure again from the start of
Program Path 3 (page 17).
2.4.2.2 Error Messages in PRLO/HI Menus
1. 2BIG: Occurs during PRLO or PRHI data entry when
displayed value exceeds 19999.
2. 2SML: Occurs during PRLO data entry when displayed
value underflows 0, or during PRHI when displayed value
underflows 1.
3. 2 LO: Occurs when stored PRHI measurement (not
display) would be less than currently stored PRLO
measurement. In other words, the capacitance being
used to set the PRHI point is less than the capacitance
used to set the PRLO.
4. 2 HI: Occurs when stored PRLO measurement (not
display) would be more than currently stored PRHI
measurement. In other words, the capacitance being
used to set the PRLO point is more than the capacitance
used to set the PRHI point.
5. UNDR: Occurs when displayed value goes below -999.
6. OVER: Occurs when displayed value goes above 19,999
(red, >10,000 LED illuminated and 9999 on the display).
19
50-621 Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches