|
822-1002-C01 Datasheet, PDF (12/40 Pages) Magnetrol International, Inc. – Kotron® Sentinel Models 822, 832 and 842 | |||
|
◁ |
5. Replace housing cover.
6. Apply power to the unit, and proceed with calibration
of instrument as described in Section 2.0, Calibration
beginning on page 10.
NOTE: Be certain to route all power and control wires through conduit
outlet only and run probe wire up through center hole in ampli-
fier housing base.
1.7.3 Relay Wiring Chart
Kotron
Power
Material
Level
Fail-safe
Relay
Coil
Relay Terminals
CM to NC CM to NO
High
On
Low
High
Fail
Low
HLFS
LLFS
HLFS
LLFS
HLFS
LLFS
HLFS
LLFS
De-energized
Energized
Energized
De-energized
De-energized
De-energized
De-energized
De-energized
Closed
Open
Open
Closed
Closed
Closed
Closed
Closed
Open
Closed
Closed
Open
Open
Open
Open
Open
NOTES AND DEFINITIONS:
1. Equipment controlled by the Kotron relays is assumed to
be powered from one source, while the Kotron unit itself is
assumed to be powered from a different source.
2. Fail means a loss of power to the Kotron unit.
3. HLFS (high level fail-safe) means a material level in the
tank which is equal to or above:
a. The setting of a narrow differential point.
b. The higher setting of a wide differential point.
4. LLFS (low level fail-safe) means a material level in the tank
which is equal to or below:
a. The setting of a narrow differential point.
b. The lower setting of a wide differential point.
5. a. When the relay coil is de-energized, a connection is
made between terminals C (common) and NC (nor-
mally closed), and there is no connection between C
and NO (normally open).
b. When the relay coil is energized, a connection is made
between terminals C and NO, and there is no connec-
tion between C and NC.
6. If Relay 1 is being used as a dedicated diagnostic alarm,
the relay will always de-energize upon fault detection.
9
50-621 Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches
|
▷ |