K3NR Datasheet, PDF (3/28 Pages) List of Unclassifed Manufacturers – High-speed, Intelligent Interface Modules
Specifications
I Ratings
Supply voltage
Operating voltage range
Power consumption (see note)
Sensor power supply
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
EMC
Approved standards
Weight
100 to 240 VAC (50/60 Hz); 12 to 24 VDC
85% to 110% of supply voltage
15 VA max. (max. AC load with all indicators lit)
10 W max. (max. DC load with all indicators lit)
80 mA at 12 VDC±10%
20 MΩ min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
±1,500 V on power supply terminals in normal or common mode ±1 µs, 100 ns for square-wave noise
with 1 ns
Malfunction: 10 to 55 Hz, 0.5-mm for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75-mm for 2 hrs each in X, Y, and Z directions
Malfunction: 98 m/s2 for 3 times each in X, Y, and Z directions
Destruction: 294 m/s2 for 3 times each in X, Y, and Z directions
Operating: −10°C to 55°C (with no icing)
Storage: −20°C to 65°C (with no icing)
Operating: 25% to 85% (with no condensation)
(EMI)
EN61326+A1
Industry
Emission Enclosure:
CISPR 11 Group 1 class A: CISRP16-1/-2
Emission AC Mains:
CISPR 11 Group 1 class A: CISRP16-1/-2
(EMS)
EN61326+A1
Industry
Immunity ESD:
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
EN61000-4-3: 10 V/m (amplitude-modulated,
80 MHz to 1 GHz) (level 3)
Immunity Fast Transient Noise: EN61000-4-4: 2 kV (power line) (level 3)
Immunity Burst Noise:
1 kV line to line (I/O signal line)
Immunity Surge:
EN61000-4-5: 1 kV line to line
2 kV line to ground (power line)
Immunity Conducted Disturbance EN61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Immunity Voltage Dip/Interrupting EN61000-4-11: 0.5 cycles, 0, 180°, 100% (rated voltage)
UL508, CSA22.2;
Conforms to EN61326+A1, EN61010-1 (IEC61010-1)
Conforms to VDE0106/P100 (finger protection) when the terminal cover is mounted.
Approx. 400 g
Note: A K3NR with DC supply voltage requires approximately 1 A DC as control power supply current the moment the K3NR is turned ON. Do not
forget to take this into consideration when using several K3NR units. When the K3NR is not in measuring operation (e.g., the K3NR has
been just turned ON or is operating for startup compensation time), the display will read “00000” and all outputs will be OFF.
Frequency/Rate Meter K3NR K-131