K3NR Datasheet, PDF (20/28 Pages) List of Unclassifed Manufacturers – High-speed, Intelligent Interface Modules
I Initial Settings
Power ON
I Parameters
Power ON
Press the Mode Key
Mode.
for 1 s min. to move to the Setting
Select the setup menu (
) with the Mode Key
and set the operating mode, the input type, and other
settings.
RUN Mode
Refer to Operation in RUN Mode.
Press the ESC Key
for 1 s.
and Up Key
If required, set a prescale value in the prescaling menu
(
).
Setting Mode 1 s
Set comparative set values in the set value menu (
).
Make settings in the option menu (
) as required.
If necessary, generate simulated input for testing the output
function in output test (
).
After completing all the settings, press the ESC Key
to
return to RUN Mode.
Measurement starts.
Prescaling
To display rotational speeds, circumferential speeds, or other
values based on input pulse calculations, the rotational speed
must be multiplied by a factor input before the input pulses are
measured. This factor is called
a prescale value.
K3NR
Proximity Sensor
Rotation speed (rpm) = f × 60 × a
Where,
f: Input pulse frequency (p/s)
a: Prescale value
If there are 5 pulses per rotation, then an accurate rotation
speed can be calculated if a = 1/5 (= 0.2 = 2 × 10-1).
In actual application, input as follows:
Mantissa X = 2.0000
Exponent Y = 10-1
Auto-zero Time (Set before use.)
In operation modes 1 to 6, the time to force-zero the frequency if
no pulse is received for a specified period can be set. This time
is called the auto-zero time. Set the auto-zero time to a value
that is somewhat longer than the longest input pulse interval. (If
the time setting is too long or if the factory-set value is used, the
display may not return to zero even if no input pulse is
received.)
Time Unit Setting
Setting
Meaning
Set in the prescaling menu
Seconds
Minutes
Minutes and seconds
Hours, minutes, and seconds
Selecting the Sensor Type
NO: Voltage NC: Voltage
pulse H
pulse L
No-contact or
voltage pulse
input
Contact input
Note: The time unit can be set
only if operating mode 6
(passing time) is
selected.
Note: If there are large
discrepancies in the
display select or .
Note, however, that the
maximum counting
frequency is 30 Hz.
Set value menu
Output test
1s
Comparative set
value bank
−
No key operation for 5 s
(See note 4.)
Comparative
set value HH
−
No key operation for 5 s
(See note 4.)
Comparative
set value H
−
No key operation for 5 s
(See note 4.)
Comparative
set value L
−
No key operation for 5 s
(See note 4.)
Comparative
set value LL
−
No key operation for 5 s
Option menu
1s
Process time for averaging
measured value
Startup
compensation time
Power failure memory
Hysteresis
Output pattern
Upper limit (H) of
linear output range
Lower limit (L) of
linear output range
Remote/local programming
No key operation for 5 s
−
No key operation for 5 s
No key operation for 5 s
−
No key operation for 5 s
No key operation for 5 s
−
No key operation for 5 s
−
No key operation for 5 s
No key operation for 5 s
K-148 Frequency/Rate Meter K3NR