English
Language : 

CCP-1-30CC Datasheet, PDF (9/12 Pages) Cooper Bussmann, Inc. – Compact Circuit Protector DIN-Rail fused disconnect switches
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
PLC fuse monitor:
Description:
A resettable three-phase
fuse monitor that integrates
with the I/O card in a
Programmable Logic
Controller (PLC).
Installed on a CCP-3-xx
Up to 60A CCP
Technical Data 1157
Effective March 2016
70 to 100A CCP
Specifications:
• Signal output to PLC:
• +24Vdc, 10mA max
• Output signals:
• Digital 0Vdc (Low), 24Vdc max (High)
• - 0Vdc Low – Fuse is good
• - 24Vdc High – Fuse has opened
When the fuse opens, the output signal is sent high and will
remain high until the unit is reset.
Agency information
• UL 98 File E155130, Guide WHTY2
• cULus to CSA Standard 22.2 No. 4-04
Rated impulse voltage
• 8kV
Local indication
• Two distinct LEDs indicate unit power (green) and open fuse
(red). Open fuse LED is resettable upon the replacement of
the fuse and the actuation of the reset switch
Flammability rating
• UL 94V0
Wiring
• For power, signal and ground connections use shielded
twisted pair 22-24AWG (0.34-0.25mm2) 300V rated wire
Packaging
• The CCP-PLC-IND is packaged individually
• A single unit monitors up to three phases. Package includes
0.110” (2.8mm) quick connects for power, signal and
ground connections
Minimum circuit voltage
• Minimum circuit voltage required across the CCP is 100Vac/dc
for the remote indication device to operate
Installation technique
• Mounts on the left side ONLY of the CCP and mechanically
interlocks with the CCP switch handle with hardware provided
IP20 Rating
• Yes
Storage and operating temperature
• -20°C to 75°C
PLC programming
• The CCP-PLC-IND signal line is designed to provide a digital
input to a PLC I/O card. In this case, a Programmable Logic
Control
program must be written to properly interpret the input signal
to the PLC. The PLC program should check for consecutive
high
signals before taking action on a critical process.
Catalog numbers
• 1-60A, CCP-PLC-IND
• 70-100A, CCP-PLC-100
Description
Max
per
CCP
Signal
output
to PLC
Min.
circuit
Volts
Agency
information
Catalog
number
Wired remote
fuse
indication for
PLC
applications
up to 60A
Wired remote
fuse
indication for
PLC
applications
70 to 100A
1 per
CCP
(1, 2- or
3-pole)
24Vdc/
10mA
100Vac
UL 98
Recognized,
cURus 22.2
No. 4-04
CCP-PLC-IND
CCP-PLC-100
De-energize all circuits before installing or removing any
CCP-PLC-IND devices and follow all prescribed safety procedures.
Eaton.com/bussmannseries