CCP-1-30CC Datasheet, PDF (2/12 Pages) Cooper Bussmann, Inc. – Compact Circuit Protector DIN-Rail fused disconnect switches | |||
|
◁ |
Technical Data 1157
Effective March 2016
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
1-, 2- and 3-pole â Class CC, midget, 10x38mm
Description:
The revolutionary Bussmann series
Compact Circuit Protector (CCP)
fused disconnect switch is 2/3 the
footprint of a traditional fusible
switch and can provide up to a high 200kA
SCCR that can help improve assembly
SCCR.
Specifications:
Ratings
⢠Volts
⢠600Vac (Class CC)
⢠240Vac (midget UL®)
⢠400Vac (midget International Electrotechnical Commission
(IEC)
⢠80Vdc (DC Class CC/UL, DC midget/IEC)
⢠Amps
⢠30A (UL)
⢠32A (IEC)
⢠SCCR
⢠200kA (Class CC)
⢠10kA (midget UL)
1-Pole DC CCP
⢠120kA (midget IEC max)
⢠20kA (DC Class CC/UL)
⢠10kA (DC midget/IEC)
Poles
⢠1-, 2- and 3-pole versions
Agency information
⢠CE
⢠RoHS compliant
⢠For Class CC fuse versions
⢠UL 98 Listed, File E302370, Guide WHTY
⢠cULus to CSA Standard 22.2 No. 4-04, File 302370,
Guide WHTY7
⢠For UL midget and 10X38 IEC fuse versions
⢠UL 508 Listed, File E320230, Guide NRNT
⢠cULus Certified 22.2 No. 14-05
⢠IEC 60947-3 AC23A
⢠IEC 60947-3 DC23A
Conductors 75°C Cu or higher
⢠Single/dual 18-6AWG solid or stranded
⢠Single 4AWG solid or stranded
Terminals
⢠Single/dual conductor box lug or fork terminal suitable for
line, load or accessory connection
Torque
⢠18-10AWG 20 Lb-In
⢠8-4AWG 35 Lb-In
Storage and operating temperature
⢠-20°C to 75°C*
* For fuse performance under or above 25°C, consult fuse performance
derating charts in the Bussmann Division publication titled Selecting
Protective Devices (SPD), data sheet No. 3002.
Flammability rating
⢠UL 94V0
Lockout/tagout provisions
⢠4mm shank lock or Brady pin-out device part number 90850
Mounting
⢠35mm DIN-Rail
Local open fuse indication minimum voltage**
⢠90Vac for AC versions
⢠12Vdc for DC versions
**Open fuse indication requires an open fuse to be in the CCP and the switch
in the ON position.
Accessories
⢠Auxiliary contacts
⢠PLC wired remote fuse indication
Shipping weight
⢠2.84 lbs (1.29 kg) per carton
Carton quantity
⢠12 poles
Features:
⢠Extremely compact design at 17.5mm wide per pole
⢠High Short-Circuit Current Ratings (SCCR) up to 200kA (UL)
and 120kA (IEC)
⢠Disconnect rated to provide means for load isolation
⢠Full voltage rated up to 600Vac or 80Vdc
⢠Class CC version is UL 98 Listed and horsepower rated, and
suitable for branch circuit disconnect and branch circuit
protection
⢠IEC 10x38 version complies with IEC 60947-3 and suitable for
branch circuit disconnect and branch circuit protection
⢠Suitable for global installations, the units comply with UL,
cULus, and IEC standards accepting UL Class CC, midget or
IEC aM and gG/gL fuses
⢠Open fuse indication:
⢠Local fuse indication lights are standard
⢠Optional wired remote open fuse indication can be utilized
to signal a PLC and open a contactor to de-energize all
phases, if required
⢠IP20 finger-safe with 10AWG (6mm2) or larger wire
⢠Built-in switch interlock prohibits removing the fuse under
load
⢠Padlockable handle for lockout/tagout procedures -
recommend using Brady pin-out device part number 90850
2
Eaton.com/bussmannseries
|
▷ |