English
Language : 

CCP-1-30CC Datasheet, PDF (4/12 Pages) Cooper Bussmann, Inc. – Compact Circuit Protector DIN-Rail fused disconnect switches
Technical Data 1157
Effective March 2016
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Motor sizing table:
LP-CC time-delay Class CC fuses
Voltage
Motor size (Hp) Motor FLA (amps)
Min (amps) Code max (amps)
Heavy start (amps)
0.167
4.4
9
15
15
115Vac, 1-phase
0.25
5.8
12
20
20
0.33
7.2
15
25
25
0.50
9.8
30
30
30
0.17
2.2
4.5
10
10
0.25
2.9
6
10
10
0.33
3.6
7
15
15
230Vac, 1-phase
0.50
4.9
10
15
15
0.75
6.9
15
25
25
1
8
25
25
30
1.5
10
30
30
30
0.50
2.5
5
10
10
0.75
3.7
7.5
15
15
200Vac, 3-phase
1
4.8
10
15
15
1.5
6.9
15
25
25
2
7.8
25
25
30
0.50
2.4
5
10
10
0.75
3.5
7
15
15
208Vac, 3-phase
1
4.6
10
15
15
1.5
6.6
15
20
25
2
7.5
15
25
30
0.50
2.2
4.5
10
10
0.75
3.2
7
10
12
230Vac, 3-phase
1
4.2
9
15
15
1.5
6
12
20
20
2
6.8
15
25
25
3
9.6
30
30
30
0.50
1.1
2.25
6
6
0.75
1.6
3.2
6
6.25
1
2.1
4.5
10
10
460Vac, 3-phase
1.5
3
6
10
12
2
3.4
7
15
15
3.00
4.8
10
15
15
5.00
7.6
25
25
30
0.50
0.9
1.8
3
3.5
0.75
1.3
2.8
6
6
1
1.7
3.5
6
6.25
575Vac, 3-phase
1.5
2.4
5
10
10
2
2.7
5.6
10
10
3.00
3.9
8
15
15
5.00
6.1
15
20
20
7.50
9
30
30
30
Note: NEMA motors only (no IEC or design B energy efficient). Minimum size if no more than 1 start/hour. Code max if low to moderate reverse/jog/plug
applications.
Heavy start permitted only if code max does not allow motor start-up. For high reverse/jog/plug applications or larger horsepower motors, Bussmann series
Class CF (Class J electrical performance) fuses are recommended. See CCP_CF with CUBEFuse™.
4
Eaton.com/bussmannseries