English
Language : 

CCP-1-30CC Datasheet, PDF (10/12 Pages) Cooper Bussmann, Inc. – Compact Circuit Protector DIN-Rail fused disconnect switches
Technical Data 1157
Effective March 2016
PLC wiring schematic:
PPLLCCpPoowweerr
supSpulpyply
+24Vdc
0Vdc/Gnd
+24Vdc
0Vdc/Gnd
PLC
Input
Card
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
CCP-PLC-IND
CCP-PLC-100
+24Vdc
0Vdc/Gnd
Connections for CCP-PLC-IND from a CCP-3-XX
to a remote monitoring device
Circuit monitoring leads
from CCP-PLC-IND
to CCP (100Vac – 600Vac)
Signal Output
10mA max.
The CCP-PLC-IND and
CCP-PLC-100 need to be
powered by the same
+24Vdc and ground
(0Vdc/Gnd return)
terminals that are feeding
the PLC input card.
If it is not, it may signal
improperly.
If feeding multiple
CCP-PLC-INDs or
CCP-PLC-100s
from different power supplies,
there must be multiple
input cards being powered
by those same power
supplies as well.
Circuit monitoring
leads from PLC
or remote monitoring
device.
Connection from CCP-PLC-IND to CCP
Connect leads from CCP-PLC-IND to the terminals as shown.
There is a dedicated terminal on the CCP to accept the spade
connectors from the CCP-PLC-IND.
NOTE: When monitoring a 1-or 2-pole CCP, trim unused leads.
10
Eaton.com/bussmannseries