English
Language : 

CCP-1-30CC Datasheet, PDF (8/12 Pages) Cooper Bussmann, Inc. – Compact Circuit Protector DIN-Rail fused disconnect switches
Technical Data 1157
Effective March 2016
Auxiliary Contacts:
Description:
NO+NC contact output to indicate
the status of the switching
mechanism on the CCP.
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Installed on a CCP-3-xx
Up to 60A CCP
70 to 100A CCP
Specifications:
• Rated ampacity
• 5A
• Rated voltage
• 240Vac
• NC/NO contacts are closed/open
when the CCP switch is in the “ON”
position (closed)
• Flammability Rating
• UL 94V0
Agency information
• UL 98 File E155130, Guide WHTY2
• cULus to CSA Standard 22.2 No. 4-04
• IEC 60947-5-1
Dimensions – mm (in)
Up to 60A CCP
1.8
Wiring
• 20-16AWG (0.5 to 1.5mm2) wire
• Torque 5 Lb-In (0.68N•m)
• For use with only 75°C Cu wire
Packaging
• The CCP-AUX and CCP-AUX-100 are packaged individually
• A single unit is capable of mounting to a 1-, 2-, or 3-pole CCP
Installation technique
2.6
33 NO
41 NC
STRIP
34 NO
1.9
42 NC
• Mounts on the right side ONLY of the CCP, and mechanically
interlocks with the CCP switch handle with hardware provided
3.7
.190
.3
IP20 rating
• Yes
70 to 100A CCP
Environmental data
1.8
• Storage and operating temperature: -20°C to 75°C
Catalog numbers
• 1-60A, CCP-AUX
• 70-100A, CCP-AUX-100
Description
Max per
CCP
Signal
output
Agency
Catalog
information number
2.9
33 NO
UL 98
Auxiliary Contacts
Recognized,
NO+NC for
1 per CCP
(1-, 2- or
5A/240Vac cURus 22.2 CCP-AUX
41 NC
Switch Status
No. 4-04,
up to 60A
3-pole)
IEC 60947-5-
1 AC-15
Auxiliary Contacts
NO+NC for
Switch Status
70 to 100A
1 per CCP
(1-, 2- or
3-pole)
5A/240Vac
UL 98
Recognized,
CSA C22.2
No. 4-04
CCP-AUX-100
De-energize all circuits before installing or removing any CCP-AUX devices
and follow all prescribed safety procedures.
STRIP
34 NO
2.2
42 NC
.190
3.7
.3
8
Eaton.com/bussmannseries