Set Point Generator
EMA / SW 24
⢠Set point generator
⢠switchable â10.5 V/+10.5 V
Set point 1 or set point 2 can be switched to
the moduleâs output as required.
The changeover is performed safely separated
via the control input E1. The output voltage val-
ues (0â¦10.5 V) can be set using the spindle
operated potentiometers SW1 and SW2. The
control input Eâ determines the polarity safely
separated
(â10.5 V ⦠0 V ⦠+10 V).
Control input E1: 0 V = set point 1,
24 V = set point 2,
Control input E2: 0 V = positive set point,
24 V = negative set point
Ordering data
Technical data
Input signal/measurement range
Control voltage
Max. input current
Display
Setting
electronic changeover switch
Type
Cat. No.
EMA/SW
1172660000
0=0 V, 1=+24 V
24 V±20 %
⤠7 mA at 24 V
each control input: red LED
via trimming potentiometer
25 rotations nom.
Output signal
Output
Output current
Load resistance
Slew-Rate
Supply voltage UB
Residual ripple
Reaction time
Isolation voltage, voltage strength
Input/output/supply
Input-Output/TS
Storage temperature
Operating temperature
Insulation coordination according to EN 50 178
Overvoltage category
Contamination class
Accessories, dimensions and connection data see page 307
adjustable from â10.5 Vâ¦+10.5 V
Voltage output selection by E1/E2
max. ±25 mA at Urated=24 Vâ
min. 400 ⦠at Urated=24 V
0.168 V/µs
24 Vâ ± 20 %, 30 mA (RL= â)
30 mV/106 kHz (at Umax)
rising 50 µs
decreasing 80 µs
1 kV-
4 kVeff
â20 °Câ¦+70 °C
0 °Câ¦+50 °C
III
2
Fig. V