8411190000 Datasheet, PDF (30/58 Pages) Weidmuller – Mini Coupler / Mini Conditioner | |||
|
◁ |
DC/DC Signal Conditioners (Configurable)
WAVEANALOG PRO DC/DC
universally adjustable via DIP switch
adjustment help via Internet
3-way-isolation
voltage supply from 20 - 230 V ac/dc
low power loss
adjustable transmission frequency
indication LED
PRO DC/DC
Approvals:
Block diagram
Ordering data
Screw connection
Tension clamp connection
Input/output
Technical data*
Input (adjustable)
Voltage uni-/bipolar adjustable
Voltage calibrated ranges
Current uni-/bipolar adjustable
Current calibrated ranges
Input resistance
at current input range < 5 mA / > 5 mA
at voltage input
Input capacity
at current input
Voltage input range < 500 mV / > 500 mV
Overload capacity
at current input range < 5 mA / > 5 mA
Voltage input range < 500 mV / > 500 mV
Output (adjustable)
Voltage uni-/bipolar adjustable
Voltage calibrated ranges
Current uni-/bipolar adjustable
Current calibrated ranges
Offset
Load
at output current
at output voltage
Offset
Residual ripple
Adjustment zero pot.
Adjustment span pot.
Gain error
Temperature coefficient
Cut-off frequeny
General
Voltage supply
Power consumption
Frequency range
Operating temperature
Storage temperature
Factory setting
Dimensions L/H/B mm
Weight
Approvals
Coordination of insulation according to EN 50178, 04/98
Rated voltage
Rated surge voltage
Overvoltage category
Contamination class
Test voltage
Type
WAS4 PRO DC/DC
WAZ4 PRO DC/DC
configurable
Cat. No.
8560740000
8560750000
20 mV ... 200 V
0 ⦠±60 mV, 0 ⦠±100 mV, 0 ⦠±150 mV, 0 ⦠±300 mV,
0 ⦠±500 mV, 0 ⦠±1V, 0 ⦠±5V, 0 ⦠±10 V, 0 ⦠±100 V
0.1 mA ... 100 mA
0 ⦠±0.3 mA, 0 ⦠±1 mA, 0 ⦠±5 mA, 0 ⦠±16 mA,
0 ⦠20 mA, 0 ⦠50 mA
approx. 100 ⦠/ approx. 5 â¦
approx. 1 Mâ¦
approx. 1 nF
approx. 1 nF / approx. 500 pF
< 75 mA / < 300 mA
max. < 20 mA / < 3 mA continuous current
0 ⦠10 V
0 ⦠±10 V, 2 ⦠10 V, 0 ⦠±5 V, 1 ⦠5 V
0 ⦠20 mV
0 ⦠±20 mA, 4 ⦠20 mA
-100%, -50%, 0%, 50%, 100% of measuring span of the
chosen output range
< 12 V (600 ⦠at 20 mA)
< 10 mA (1 K⦠at 10 V)
20 µA and. 10 mV
< 10 mVeff
+25% measuring span of the chosen output range
0.33 ... 3.30 x end value of chosen input range
< 0.1% of FS
< 60 ppm/K of FS
> 10 kHz, < 10 Hz switch
20 ... 230 V ac/dc +10%
approx. 1 W
48 ... 62 Hz
-10 °C ... +70 °C
-40 °C ... +85 °C
0 ... 10 V / 0 ... 10 V 10 Hz
92.4 / 112.5 / 12.5
approx. 100 g
CE, cUL, GL
600 V
5 kV, 1.2/50 us, acc. to IEC 255-4
III
2
4 KVeff input against output against auxiliary power
Standards/specifications
EMC standards
EN 50178
DIN EN 61326, EN 61326/A1, EN 50081-2, EN 61000-6-2
NEW
Adjustment help WAVETOOL
The service tool enables quick and uncompli-
cated configuration of WAVEANALOG PRO.
Download from Internet:
http://www.weidmueller.de
â Products â Downloads (see page 192)
Switch position/setting options
Switch
Input
S1
S2
Input range
1234 1234
0 ⦠±60 mV
0 ⦠±100 mV
0 ⦠±150 mV
0 ⦠±300 mV
0 ⦠±500 mV
0 ⦠±1 V
0 ⦠±5 V
0 ⦠±10 V
0 ⦠±100 V
0 ⦠± ~0.3 mA
0 ⦠±1 mA
0 ⦠±5 mA
0 ⦠±10 mA
0 ⦠±20 mA
0 ⦠±50 mA
0 ⦠±20 mA*
*Offset conversion not calibrated
Switch S2
4
calibrated ranges
Span pot. activated: input range x 0.33 ... x 3.30
Output
Output range
0 ⦠±10 V
2 ⦠10 V
0 ⦠±5 V
1â¦5V
0 ⦠±20 mA
4 ⦠20 mA
Switch
S1
S3
567 12
Offset
S1
S2
(in % of output voltage)
8 9 10 5
0%
-100 %
-50 %
+50 %
+100 %
Zero pot. activated: additional ±25 %
Switch S3
3
Bandwidth 10 kHz
Bandwidth 10 Hz
Set range can be documented on side of housing.
= on
= off
Dimensions and accessories
see page 298 + 308
*TU = 23 °C single module
185
|
▷ |