English
Language : 

8411190000 Datasheet, PDF (36/58 Pages) Weidmuller – Mini Coupler / Mini Conditioner
Thermo Signal Isolating Transformers (Configurable)
WAVEANALOG PRO Thermo
3-way-isolation
thermocouples
K, J, T, E, N, R, S, B configurable
temperature range
-200 °C ... +1820 °C
no adjustment necessary
cold junction compensation
configurable output signal
cross-connectable voltage supply
via cross-connectors
Approvals:
PRO Thermo
Adjustment help
WAVETOOL
This service tool
enables quick and
uncomplicated config-
uration of
WAVEANALOG PRO.
Download from the
Internet:
http:
//www.weidmueller.de
→ Products →
Downloads
(see page 192)
Block diagram
Selection the
thermocoupler
SW1
Type
123
K
J
T
E
N
R
S
B
NEW
Selection of minimum
temperature
SW1
␽min
4567
0°C
-10°C
-20°C
-30°C
-40°C
-50°C
-100°C
-150°C
-200°C
+50°C
+100°C
+150°C
+200°C
+250°C
500°C
Special range
Ordering data
Screw connection
Tension clamp connection
Input/output
Technical data*
Input (adjustable)
Accuracy at Tu = 23 °C
Output (adjustable)
Output voltage
Offset voltage
Load resistance
Output current
Offset current
Load resistance
Step response
at connected filter function
Max. wire resistance
Open circuit recognition
Range of man. fine adjustment
Status LED:
General
Supply voltage:
Power consumption:
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
Standards/specifications
EMC standards
Factory setting
Dimensions L/H/W mm
Weight
Approvals
Dimensions and accessories see
* TU = 23 °C single module
Type
WAS5 PRO Thermo
WAZ5 PRO Thermo
configurable
Cat. No.
8560720000
8560730000
Thermocouples acc. to EN 60584-1
Type K, J, E, N, R, S, B via DIP switch selectable
Type K -200°C ...-150°C ± (5K + 0.1% of set range)
-150°C ...1200°C ± (3K + 0.1% of set range)
1200°C ...1372°C ± (4K + 0.1% of set range)
Type J -200°C ...-150°C ± (4K + 0.1% of set range)
-150°C ...1200°C ± (3K + 0.1% of set range)
Type T -200°C ...-150°C ± (5K + 0.1% of set range)
-150°C ...400°C ± (3K + 0.1% of set range)
Type E -200°C ...-150°C ± (4K + 0.1% of set range)
-150°C ...1000°C ± (3K + 0.1% of set range)
Type N -200°C ...-150°C ± (6K + 0.1% of set range)
-150°C ...1300°C ± (3K + 0.1% of set range)
Type R -50°C ...200°C ± (10K + 0.1% of set range)
200°C ...1760°C ± (6K + 0.1% of set range)
Type S -50°C ...200°C ± (10K + 0.1% of set range)
200°C ...1760°C ± (6K + 0.1% of set range)
Type B 50°C ...250°C ± (25K + 0.1% of set range)
250°C ...500°C ± (10K + 0.1% of set range)
500°C ...1820°C ± (6K + 0.1% of set range)
0...10 V
Max. 0.05 V
≥ 1 KΩ
0/4 ... 20 mA
max. 100 µA
≤ 600 Ω
max. 1.4 s
max. 7.5 s
50 Ω for 3- and 4-wire
Output signal > 10 V or > 20 mA, LED blinks
≥ ±5%
Module active: LED lights up / open circuit: LED blinks
Error: LED off
18 Vdc ... 24 Vdc ... 30 Vdc
800 mV ... 850 mW ... 950 mW @ I output = 20 mA
≤2A
0 °C ... +55 °C
-20 ... +85 °C
Selection of
temperature span
SW2
Span 1 2 3 4 5
100°C
150°C
200°C
250°C
300°C
350°C
400°C
450°C
500°C
550°C
600°C
650°C
700°C
750°C
800°C
850°C
900°C
950°C
1000°C
1050°C
1100°C
1150°C
1200°C
1250°C
1300°C
1350°C
1400°C
1450°C
1500°C
1600°C
1700°C
1800°C
Selection of
output
SW2
Output
67
0...10V
0...20mA
4...20mA
Switching on the
manual fine adjustment
SW1
man. adjust.
8
off
on
Switching on the
filter function
SW2
Filter
8
off
on
= on
= off
Coordination of insulation acc. to DIN EN 50178, 04/98
Rated voltage
300 V
Surge voltage
4 kV
Overvoltage category
III
Contamination class
2
Clearance & creep. distance 3 mm
Test voltage
2 kVeff
EN 50178, IEC751
EN 50081, EN50082, EN55011
Type K 0 ... 1000 °C / 4 ... 20 mA; no filter;
No manual fine adjustment
92.4 / 112.5 / 17.5
100 g
CE, cUL, GL
Page 298 + 308
191