English
Language : 

8411190000 Datasheet, PDF (47/58 Pages) Weidmuller – Mini Coupler / Mini Conditioner
Current Monitoring
• For AC/DC
• Adjustable switching threshold
• Relay output
SMSI DC R
With adjustable switching threshold
up to 250 mA
SMSI AC R
With adjustable switching threshold
up to 250 mA
Ordering data
Type
Cat. No.
SMSI 0.25 DC R 1156660000
Technical data
Measurement circuit voltage
Max. permissible current in measurement circuit
Rated consumption ~ (VA)
Voltage drop at input
Adjustable switching threshold
Hysteresis between turn-on and turn-off point
Activation time tA
Reaction time tR
Recovery
Output voltage
Max. continuous output current
Auxiliary voltage
Rated consumption auxiliary voltage
Max. switching current
Contact
Contact material
10 V…250 Vdc
350 mA
750 mVA (l = 250 mA)
≤ 3 V (I = 250 mA)
40 mA…250 mA–
2% (250 mA)<lHY<10% (40 mA)
-
≤ 12 ms
-
250 V
3A
24 V~ ±10%
250 mW/450 mVA
8A
1 NO1)
AgNi, gold-flashed
Storage temperature
Ambient temperature
–, assembled without spacing on TS
–, assembled with ≥ 20 mm spacing on TS
Coordination of insulation to DIN VDE 0160,Draft 11/94
Overvoltage category, input, output
Overvoltage category, input1-input2,
Output1-output 2, input-output
Contamination class
–25 °C…+60 °C
–25 °C…+40 °C
–25 °C…+50 °C
II
III
2
Dimensions and connection data
see page 307
Fig. V
1) NC on request
202
Type
Cat. No.
SMSI 0.25 AC R 1159960000
10 V…250 Vac
300 mA
1075 mVA (l = 250 mA)
≤ 3 V (I = 250 mA)
40 mA…250 mA~
≤ 5%
≤ 25 ms
≤ 15 ms
-
250 V
3A
24 V~ ±10%
250 mW/450 mVA
8A
1 NO1)
AgNi, gold-flashed
–25 °C…+60 °C
–25 °C…+40 °C
–25 °C…+50 °C
II
III
2
Fig. V