English
Language : 

8411190000 Datasheet, PDF (19/58 Pages) Weidmuller – Mini Coupler / Mini Conditioner
Passive Isolator DC/DC
WAVEANALOG DC/DC
input loop powered
galvanic isolation
1-, 2-channel versions
low power consumption
safe separation
CCC LP (1 channel)
0(4) ... 20 mA / 0(4) ... 20 mA
Approvals:
Block diagram
CCC LP (2 channel)
0(4) ... 20 mA / 0(4) ... 20 mA
Ordering data
Screw connection 1 channel
Tension clamp connection 1 channel
Screw connection 2 channel
Tension clamp connection 2 channel
Input/output
Type
WAS5 CCC LP
WAZ5 CCC LP
Cat. No.
8444950000
8444960000
0(4) ... 20 mA / 0(4) ... 20 mA
Technical data* (per channel)
Input signal
Input voltage max.
Input current max
Operating current
Voltage drop
Output signal
Load resistance
Accuracy at Tu=23 °C
Influence of load resistance
Temperature coefficient
Set time
Residual ripple
Chopper frequency
0 ... 20 mA (4 ... 20 mA)
18 V
50 mA
< 100 µA
approx. 3 V at RL= 0 Ω
Iin = 20 mA
approx. 13 V at RL= 500 Ω
at Iin = 20 mA
0 ... 20 mA (4 ... 20 mA)
≤ 500 Ω
< 0.1% of FS
< 0.1% from measurement value
per 100 Ω load resistance
50 ppm / K of FS
4.5 ms at 500 Ω working resistance
< 20 mVeff
approx. 170 kHz
General
Operating temperature
Storage temperature
Dimensions L / H / W mm
Approvals
-25 °C ... +70 °C
-40 °C ... +80 °C
92.4 / 112.5 / 17.5
CE, UL, CSA, GL
Coordination of insulation according to EN 50178, 04/98 (safe separation)
Rated voltage
300 V
Rated surge voltage
6 kV
Overvoltage category
III
Contamination class
2
Clearance and creepage distance
≥ 5.5 mm
Isolation voltage, voltage strength
Input/output, channel / channel
Input/output to mounting rail
Standards/specifications
4 kVeff / 1 s
4 kVeff / 1 min
EN 50178 (safe separation)
EMC standards
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
Page 298 + 308
*TU = 23 °C single module
174
Type
Cat. No.
WAS5 CCC LP
8463580000
WAZ5 CCC LP
8463590000
0(4) ... 20 mA / 0(4) ... 20 mA
0 ... 20 mA (4 ... 20 mA)
18 V
50 mA
< 100 µA
approx. 3 V at RL= 0 Ω
Iin = 20 mA
approx. 13 V at RL= 500 Ω
at Iin = 20 mA
0 ... 20 mA (4 ... 20 mA)
≤ 500 Ω
< 0.1% of FS
< 0.1% from measurement value
per 100 Ω load resistance
50 ppm / K of FS
4.5 ms at 500 Ω working resistance
< 20 mVeff
approx. 170 kHz
-25 °C ... +70 °C
-40 °C ... +80 °C
92.4 / 112.5 / 17.5
CE, UL, CSA, GL
300 V
6 kV
III
2
≥ 5.5 mm
4 kVeff / 1 s
4 kVeff / 1 min
EN 50178 (safe separation)
EN 50081, EN 50082,
EN 55011
Page 298 + 308