Bits 4 - 2 - SPIN_LVL[2:0] - Determines the final drive level that is used by the Spin Up Routine as
shown in Table 6.36.
Table 6.36 Spin Level
SPIN_LVL[2:0]
2
1
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
SPIN UP DRIVE LEVEL
0
0
30%
1
35%
0
40%
1
45%
0
50%
1
55%
0
60% (default)
1
65%
Bit 1 -0 - SPINUP_TIME[1:0] - determines the maximum Spin Time that the Spin Up Routine will run
for (see Section 5.2). If a valid tachometer measurement is not detected before the Spin Time has
elapsed, then an interrupt will be generated. When the RPM-based Fan Speed Control Algorithm is
active, the fan driver will attempt to re-start the fan immediately after the end of the last spin up attempt.
The Spin Time is set as shown in Table 6.37.
Table 6.37 Spin Time
SPINUP_TIME[1:0]
1
0
0
0
0
1
1
0
1
1
TOTAL SPIN UP TIME
250 ms
500 ms (default)
1 sec
2 sec
6.22 Fan Max Step Register
Table 6.38 Fan Max Step Register
ADDR
R/W
REGISTER
B7 B6 B5 B4 B3 B2
B1
B0
DEFAULT
47h
R/W Fan Max Step
-
-
32 16 8
4
2
1
10h
The Fan Max Step Register, along with the Update Time, controls the ramp rate of the fan driver
response calculated by the RPM-based Fan Speed Control Algorithm. The value of the registers
represents the maximum step size each fan driver will take between update times (see Section 6.18).