DC12-48V (120V), 20A, DUAL REDUNDANCY MODULE
9. EMC
The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and
light industry environment without any restrictions. A detailed EMC report is available on request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3 80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Surge voltage on input lines EN 61000-4-5
Surge voltage on output lines EN 61000-4-5
Input lines
Output lines
+/- Æ Chassis ground
+/- Æ Chassis ground
2kV
Criterion A
2kV
Criterion A
1kV
Criterion A
1kV
Criterion A
Conducted disturbance
EN 61000-4-6 0.15-80MHz
10V
Criterion A
Power-frequency magnetic
field *)
EN 61000-4-8 50Hz
30A/m
Criterion A
Criterions:
A: Redundancy module shows normal operation behavior within the defined limits.
Notes:
*) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall
elements, electrodynamic microphones, etc.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Class B, input lines *)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Class B, output lines *)
Radiated emission
EN 55011, EN 55022
Class B
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) Provided, that power sources connected on the inputs fulfill the class B requirements too.
Apr. 2014 / Rev. 1.4 DS-YR2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted