English
Language : 

YR2.DIODE Datasheet, PDF (17/19 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YR2.DIODE
DC12-48V (120V), 20A, DUAL REDUNDANCY MODULE
17.6. EXAMPLE: REDUNDANCY FOR CONTROLS
The example shows a cost effective solution to get redundant power for a PLC or controller system.
In many cases, two power supplies are used; one for the demanding loads and another one for the controls and
sensitive loads. The power supply for the demanding loads can be used as a redundant source to supply the controls.
Traditional approach:
PS1
Load
PS2
PLC
Improved approach:
PS1
Load
PS2
YR2
PLC
Fig. 17-4 Wiring diagram, redundancy for sensitive loads
Failure
Monitor
Heavy
Loads
e.g. Motors
++ --
24V,20A Adj
DCok
Overload
QT20.241
Power
Supply
L1 L2 L3 PE
+- +-
IN 1 IN 2
YR2.Diode
Redundancy
Module
OUT
+-
++- -
24V,
5A
Adj
DCok
Overload
QS5.241
Power
Supply
L N PE
I II
L1
L2
L3
N
PE
optional
I
Note: Use separate mains systems for each power supply whenever it is possible
Sensitive
Load
e.g.
Controller
Apr. 2014 / Rev. 1.4 DS-YR2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
17/19