English
Language : 

YR2.DIODE Datasheet, PDF (16/19 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YR2.DIODE
DC12-48V (120V), 20A, DUAL REDUNDANCY MODULE
17.4. EXAMPLE: N+1 REDUNDANCY UP TO 30A
N+1 Redundancy up to 30A requires four 10A power supplies and two YR2.DIODE redundancy modules.
Fig. 17-2 Wiring diagram, n+1 Redundancy, 30A output current
++ --
24V,10A Adj
DCok
Overload
QS10.241
Power
Supply
L N PE
+- +-
IN 1 IN 2
YR2.Diode
Redundancy
Module
OUT
+-
++ --
24V,10A Adj
DCok
Overload
QS10.241
Power
Supply
L N PE
++ --
24V,10A Adj
DCok
Overload
QS10.241
Power
Supply
L N PE
+- +-
IN 1 IN 2
YR2.Diode
Redundancy
Module
OUT
+-
++ --
24V,10A Adj
DCok
Overload
QS10.241
Power
Supply
L N PE
Failure
Monitor
I
L
N
PE
I
I
I
optional
Note: Use separate mains systems for each power supply whenever it is possible
30A
Load
17.5. EXAMPLE: BATTERY BACK-UP
A battery back-up with 10A requires one 10A power supply and one YR2.DIODE redundancy module.
Please note:
Set output voltage of power supply to 26.5Vdc minimum to ensure, that the load current is delivered from the power
supply and not from charger (battery). Use a fuse between battery and YR2.DIODE!
Fig. 17-3 Wiring diagram, 10A Battery back-up
I
24V Battery
-
Battery
Charger
L
N
PE
++ --
24V,10A Adj
DCok
Overload
QS10.241
Power
Supply
L N PE
+- +-
IN 1 IN 2
Failure
Monitor
YR2.Diode
Redundancy
Module
OUT
+-
optional
10A
Load
Apr. 2014 / Rev. 1.4 DS-YR2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany