17.7. EXAMPLE: DECOUPLING OF BRANCHES
Buffer energy supplied from a DC-UPS or buffer module is not wasted in “power branches”.
Please note:
Set output voltage of the power supply to a level that the buffer unit or DC-UPS will not start unexpected. Take the
voltage drop of the YR2.DIODE into account.
Fig. 17-5 Wiring diagram, decoupling of buffered branches
Failure
Monitor
Load
e.g. Motor
++ --
24V,20A Adj
DCok
Overload
QT20.241
Power
Supply
L1 L2 L3 PE
+- +-
IN 1 IN 2
YR2.Diode
Redundancy
Module
OUT
+-
Buffer
Module
+-
I II
L1
L2
L3
PE
optional
Note: Use separate mains systems for each power supply whenever it is possible
Buffered
Load
e.g.
Controller
17.8. USE IN A TIGHTLY SEALED ENCLOSURE
When the redundancy module is installed in a tightly sealed enclosure, the temperature inside the enclosure will be
higher than outside. The inside temperature defines the ambient temperature for the redundancy module.
Results from such an installation:
Power supply is placed in the middle of the box, no other heat producer inside the box
Enclosure:
Load:
Input:
Temperature inside enclosure:
Temperature outside enclosure:
Temperature rise:
Rittal Typ IP66 Box PK 9516 100, plastic, 110x180x165mm
24V, 16A; (=80%) load is placed outside the box
24Vdc
57.8°C (in the middle of the right side of the power supply with a distance of 2cm)
24.6°C
33.2K
Apr. 2014 / Rev. 1.4 DS-YR2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted