14. ENVIRONMENT
Operational temperature1) -25°C to +70°C (-13°F to 158°F)
reduce output power according Fig. 14-1
Storage temperature
-40 to +85°C (-40°F to 185°F)
for storage and transportation
Output de-rating
3.2W/°C
45-60°C (113°F to 140°F)
6W/°C
60-70°C (140°F to 158°F)
Humidity2)
5 to 95% r.H.
IEC 60068-2-30
Vibration sinusoidal3)
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock3)
30g 6ms, 20g 11ms
IEC 60068-2-27
3 bumps / direction, 18 bumps in total
Altitude
0 to 6000m (0 to 20 000ft)
reduce output power or ambient temperature
above 2000m sea level.
Altitude de-rating
15W/1000m or 5°C/1000m
above 2000m (6500ft), see Fig. 14-2
Over-voltage category
not applicable
The concept of the overvoltage category is
used for equipment energized directly from
the low voltage mains (IEC 60664-1 §4.3.3.2.1).
Degree of pollution
2
IEC 62477-1, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
Corrosive gases
ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4
Audible noise
Some small audible noise will be emitted from the power supply.
1) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
2) Do not energize while condensation is present
3) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard mounting
orientation. Higher levels allowed when using the wall mounting bracket ZM2.WALL.
Fig. 14-1 Output current vs. ambient temp.
Allowable Output
Current at 24V
12A
continuous
10
short
term
8
6
4
2
0
-25
Ambient Temperature
0
20 40 60 70°C
Fig. 14-2 Output current vs. altitude at 24V
Allowable Output
Current at 24V
12A
BC
10
A
8
short term
6
4 A... Tamb < 60°C
2
B... Tamb < 50°C
C... Tamb < 40°C
0
0
2000
4000
Altitude
6000m
Jul. 2017 / Rev. 1.1 DS-CD10.241-EN All parameters are typical values at 24V, 10A, 24Vdc input voltage, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany