PAS395 Datasheet, PDF (10/14 Pages) PULS GmbH – Charger for EDLC Capacitors (Ultra-Caps)
11 EMC
EMC Immunity
Electrostatic discharge
Electromagnetic RF field
Fast transients (Burst)
Surge voltage on input
Surge voltage on output
Surge voltage on signals
Conducted disturbance
Mains voltage dips
Voltage interruptions
Powerful transients
Generic standards: EN 61000-6-1 and EN 61000-6-2
EN 61000-4-2
Contact discharge
Air discharge
EN 61000-4-3 80MHz-2.7GHz
EN 61000-4-4
Input lines
Output lines
Signal lines
EN 61000-4-5
EN 61400-24
LN
LN
EN 61000-4-5
EN 61400-24
L  PE
L  PE
EN 61000-4-5
EN 61400-24
+-
+-
EN 61000-4-5
EN 61400-24
+ / -  PE
+ / -  PE
EN 61000-4-5
EN 61400-24
signal  PE
signal  PE
EN 61000-4-6 0.15-80MHz
EN 61000-4-11
0% of 220Vac (=0V)
40% of 220Vac (=88V)
70% of 220Vac (=154V)
EN 61000-4-11 0% of 220Vac (=0V)
VDE 0160
over entire load range
8kV
15kV
20V/m
4kV
4kV
2kV
2kV
LPZ 2
4kV
LPZ 2
1kV
LPZ 2
4kV
LPZ 2
1kV
LPZ 2
20V
20ms
200ms
500ms
5000ms
750V, 1.3ms
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion C *)
Criterion A
Criterion C
see note M
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the
power supply will occur.
*) signal status and LED will remain appropriate (= Criterion A)
Note M: The protection circuit switches off the converter for approx. 2 seconds, which is not considered to be a problem for the
charging process.
EMC Emission
Generic standards: EN 61000-6-4
Conducted emission
EN 55011, EN 55022, FCC Part 15, CISPR 11,
CISPR 22
Input lines:
Class A
Signal lines:
Class A
Radiated emission
EN 55011, EN 55022
Class A
Harmonic input current
EN 61000-3-2
Voltage fluctuations, flicker EN 61000-3-3
Class A fulfilled (active PFC)
fulfilled *)
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) Tested with constant current loads, non pulsing
This document is proprietary. Any dispatch or disclosure of content is authorized only after written authorization by PULS GmbH.
All parameters are specified at 400V, 2.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
Specification: SP-PAS395 Rev: 3.1
Date: 2013/01/19
10-14