English
Language : 

K34-C1 Datasheet, PDF (15/16 Pages) Omron Electronics LLC – An Ideal Indicator for OK/NG Judgements in Automated and Picking Machines, Measuring Factors such as Pressure, Load, Torque, and Weight Using Load Cell Signal Input.
■ Wiring Precautions
• For terminal blocks, use the crimp terminals suitable for M3 screws.
• Tighten the terminal screws to the recommended tightening torque
of approx. 0.5 N⋅m.
• To prevent inductive noise, separate the wiring for signal lines from
that for power lines.
Wiring
• Use the crimp terminals suitable for M3 screws shown below.
5.8 mm max.
K3HB-V
■ Mounting Method
1. Insert the K3HB into the mounting cutout in the panel.
2. Insert watertight packing around the Unit to make the mounting
watertight.
Watertight
packing
5.8 mm max.
Unit Stickers
• Select the appropriate units from the unit sticker sheets provided
and attach the sticker to the Indicator.
3. Insert the adapter into the grooves on the left and right sides of
the rear case and push until it reaches the panel and is fixed in
place.
Adapter
Note: When using for meters, such as weighing meters, use the units
specified by regulations on weights and measures.
■ LCD Field of Vision
The K3HB is designed to have the best visibility at the angles shown
in the following diagram.
10°
30°
■ Rubber Packing
(Sold Separately)
K32-P1
If the rubber packing is lost or damaged, it can
be ordered using the following model number:
K32-P1.
(Depending on the operating environment
deterioration, contraction, or hardening of the
rubber packing may occur and so, in order to
ensure the level of waterproofing specified in
NEMA4, periodic replacement is
recommended.)
Note: Rubber packing is provided with the
Controller.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
15