ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating/Test Voltage
Conditions
Input to Output – Reinforced
Input to Chassis – Basic
Output to Chassis – Functional
Min
Typ
3000
1500
500
Max Units
Vrms
Vrms
Vdc
STATUS INDICATORS (LEDs)
Status Indicators
Input OK (Green)
Output OK (Green) Fault5 (Yellow)
AC present and within the regulation range;
Standby - ON; Main Output – OFF
AC present, but its level is not within the required regulation range
When hot-unplugging the power supply from a power shelf4
Solid Green
Blinking
Off
Blinking Green at 1Hz rate
(0.5s on, 0.5s off)
Off
Off
Blinking Green at 1Hz rate
(0.5s on, 0.5s off)
Off
Off
AC input voltage is not present
Off
Off
Off
AC present and within the regulation range;
Standby – ON, Main Output – ON and both within the regulation range
AC present and within the regulation range;
Standby - ON; Main Output - ON; power supply is in a power limit or in an overcurrent condition.
Solid Green
Solid Green
Solid Green
Off
Solid Green
On
Any warning Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP, FAN)
No Change
No Change
Blinking 1Hz
Any Fault Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP, FAN)
Depends on PS Status
Depends on PS Status On
4 The Input OK LED blinks to indicate that there is still energy inside the power supply until the input bulk capacitors are completely discharged or the housekeeping circuit is shut
down.
5 The Fault LED and PS Fault signal shall be turned on to indicate that there is one or more of the following internal faults currently detected inside the power supply:
• VSB out of range
• Output stage OT
• Fan fault
• ORING fault (Output voltage less than bus voltage)
• OC shutdown
• OT shutdown
• OV shutdown
• Input stage OT
• Fault induced shutdown occurred
• Thermal sensor fault
• Vout out of range
• PFC Boost Vbulk fault
As soon as all of the above faults are removed and the power supply operates normally, the Fault LED and PS Fault signal shall be turned off.
LED Definition: Three LEDs shall be located on the front faceplate, and these are:
LED
Status
Input OK = ON
Output OK = ON
Fault = ON