English
Language : 

D2U5T-H3-7000-54-HU4C Datasheet, PDF (2/8 Pages) Murata Manufacturing Co., Ltd. – AC-DC Three Phase Power Converter
D2U5T-H3-7000-54-HU4C
AC-DC Three Phase Power Converter
OUTPUT VOLTAGE CHARACTERISTICS
Output Parameter
Output Current
54V
3.3VSB
5VSB
Voltage Set Point
Voltage Droop
Line Regulation
Ripple Voltage & Noise1
Load Capacitance
Voltage Set Point
Line and Load Regulation
Ripple Voltage & Noise2
Output Current
Load Capacitance
Voltage Set Point
Line and Load Regulation
Ripple Voltage & Noise2
Output Current
Load Capacitance
Conditions
Range 1
Range 2
@32.4A Range 1
@64.8A Range 2
Min to Max Current, Range 1
Min to Max Current, Range 2
20MHz Bandwidth
20MHz Bandwidth
Min
Typ
Max Units
0
64.8
Adc
0
129.6
54
54
Vdc
1. 5V
3.0V
0.1
%
0.5
Vp-p
470
5000 μF
3.30
Vdc
3.14
3.46
100 mVp-p
0
6
A
20
1000 μF
5.00
Vdc
4.76
5.24
100 mVp-p
0
4
A
20
1000 μF
1 Ripple and noise are measured with 2.2μF (X7R 100V) ceramic + 180μF (UCC EKY) of electrolytic de-coupling capacitors at the output connector load side. A short coaxial cable
with 50Ω scope termination is used.
2 Ripple and noise are measured with 0.1μF of ceramic capacitance and 10 μF of tantalum capacitance across the power supply outputs at the output connector load side. A short
coaxial cable with 50Ω scope termination is used.
C1
2.2μF X7R 100V
+
54V Output
–
+
C2
180μF 63V UCC EKY
T1
COAX
RG587U
R1
50Ω
SCOPE
+
VSB
–
+
C3
C4
100NF X7R 25V 10μF 10V TANT
T2
COAX
RG587U
R2
50Ω
SCOPE
OUTPUT CHARACTERISTICS
Parameter
Startup Time
Transient Response3
Current sharing accuracy (up to 3 in parallel)
Hot Swap Transients
Holdup Time
Conditions
AC ramp up
54V, 50-100% load step, 0.1A/μs di/dt
5VSB, 50-100% load step, 1A/μs di/dt
3.3VSB, 50-100% load step, 1A/μs di/dt
54V @100% load
All outputs within regulation
54V @100% load
VSB @100% Load
3 Minimum output capacitance to be 470μF (low ESR).
www.murata-ps.com/support
Min
Typ
Max Units
3
s
2.4
Vp-p
250
mVp-p
250
mVp-p
+/-10 %
12
ms
100
D2U5T-H3-7000-54-HU4C.A02 Page 2 of 8