English
Language : 

D1U54P-W-650-12-HBXC Datasheet, PDF (8/9 Pages) Murata Power Solutions Inc. – 54mm 1U Front End AC-DC Power Supply Converter
WIRING DIAGRAM FOR OUTPUT
D1U54P
V1_SENSE
(Main Output Remote Sense)
E3
6 -10
+12V Main Output
D1U54P-W-650-12-HBxC Series
54mm 1U Front End AC-DC Power Supply Converter
Dotted lines show optional remote sense connections.
Optional remote sense lines can be attached to a load that is a distance
away from the power supply to improve regulation at the load.
V1_SENSE
(Main Output Remote Sense)
E3
+12V Main Output
6-10
D1U54P
1-5
+12V Main Output Return
+12V
Load
+12V Main Output Return
1-5
D3
B5
A1, B1, C1,
D1, E1
B4
A2, B2
V1_SENSE_R
ISHARE
VSB
PS_ON
VSB_Return
FET, BJT, wire or
switch (debounced)
to turn on +12V
Main Output
VSB
Load
A5
PS_KILL
V1_SENSE_R
ISHARE
VSB
PS_ON
D3
B5
A1, B1, C1,
D1, E1
B4
VSB_Return A2, B2
A5
PS_KILL
CURRENT SHARE NOTES
1. Main Output: Current sharing is achieved using the active current share method details.)
2. Current sharing can be achieved with or without the remote (V_SENSE) connected to the common load.
3. +VSB Outputs can be tied together for redundancy but total combined output power must not exceed the rated standby power. The +VSB output has an internal ORING
MOSFET for additional redundancy/internal short protection.
4. The current sharing pin B5 is connected between sharing units (forming an ISHARE bus). It is an input and/or an output (bi-directional analogue bus) as the voltage on the
line controls the current share between sharing units. A power supply will respond to a change in this voltage but a power supply can also change the voltage depending
on the load drawn from it. On a single unit the voltage on the pin (and the common ISHARE bus would read 8VDC at 100% load. For two units sharing the same load this
would read 4VDC for perfect current sharing (i.e. 50% load per unit).
5. The load for both the main 12V and the VSB rails at initial startup shall not be allowed to exceed the capability of a single unit. The load can be increased after a delay of
3sec (minimum), to allow all sharing units to achieve steady state regulation.
MECHANICAL DIMENSIONS
www.murata-ps.com/support