D1U54P-W-650-12-HBXC Datasheet, PDF (3/9 Pages) Murata Power Solutions Inc. – 54mm 1U Front End AC-DC Power Supply Converter
D1U54P-W-650-12-HBxC Series
54mm 1U Front End AC-DC Power Supply Converter
PROTECTION CHARACTERISTICS
Output Parameter
Conditions
Min.
Typ.
Max.
Overtemperature (intake) Autorestart with 4°C hysteresis for recovery (warning issued at 70°C)
75
Overvoltage
Latching
13.0
14.5
The output shall shutdown when an overcurrent condition is detected.
It will auto restart after 1sec; however if the overcurrent condition is
12V
redetected the output will once again shutdown.
Overcurrent (target)
The output will once again re-start, however if the overcurrent
60
70
condition persists it will latch of after the fifth unsuccessful attempt.
To reset the latch it will be necessary to toggle the PS_ON_L signal
(B4) or recycle the incoming AC source.
Overvoltage
Latching
13.0
14.5
The output shall shutdown when an overcurrent is detected.
12VSB
It will auto restart after 2sec; however if the overcurrent is re-detected
Overcurrent
the output will once again shutdown.
2.5
3.5
This cycle will occur indefinitely while the overcurrent condition
ISOLATION CHARACTERISTICS
i
Parameter
Conditions
Min.
Typ.
Max.
Insulation Safety Rating
Input to Output - Reinforced
3000
Input to Chassis - Basic
1500
Isolation
Output to Chassis
500
Units
°C
V
A
V
A
Units
Vrms
Vrms
Vdc
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Voltage Fluctuation and Flicker
Conducted Emissions
Standard
IEC/EN 61000-3-2
IEC/EN 61000-3-3
FCC 47 CFR Part 15
CISPR 22/EN55022
Compliance
Complies
Complies
Class A with 6dB margin
ESD Immunity
Radiated Field Immunity
Electrical Fast Transients/Burst Immunity
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
Level 4 criteria A
Level 3 criteria B
Level 3 criteria A
Surge Immunity
IEC/EN 61000-4-5 • 6kV common mode and differential mode, unit shall fail safely#.
• 4kV common mode and differential mode, unit shall survive; the output may shut down and recover
automatically (Criteria B) or require manual intervention (Criteria C)#.
RF Conducted Immunity
• 2kV common and differential mode, unit passes criteria A (normal performance)*
IEC/EN 61000-4-6 Level 3 criteria A
Magnetic Field Immunity
IEC/EN 61000-4-8 3 A/m criteria B
230Vin, 80% load, Phase 0°, Dip 100% Duration 10ms (A)
Voltage Dips, Interruptions
IEC/EN 61000-4-11 230Vin, 50% load, Phase 0°, Dip 100% Duration 20ms (VSB:A, V1:B)
230Vin, 100% load, Phase 0°, Dip 100% Duration > 20ms (VSB, V1:B)
* Impedance is 2 ohms for ±2KV differential and common mode to comply with NEBS GR-1089 limits. Maximum load capacitance is required for these tests.
# Tests above ±2KV will be performed for information purposes to IEC/EN66100-4-5 with 12ohm impedance, differential & common mode.
STATUS INDICATORS
LED NAME
LED MODE
LED STATE/OPERATION
DESCRIPTION
Input
OK
Solid Green
Input voltage operating within normal specified range
Input
OV/UV WARNING
Input
OFF OR FAULT
Blinking Green
Off
Input voltage operating in:
1) overvoltage warning, or
2) undervoltage warning range
Input voltage operating:
1) above overvoltage range, or
2) below undervoltage range, or
3) not present
Output
POWER GOOD
Output
STANDBY
Output
WARNING
Output
FAULT
www.murata-ps.com/support
Solid Green
Blinking Green
Blinking Amber
Solid Amber
Main output and standby output enabled with no power supply
warning or fault detected
Standby output enabled with no power supply warning or fault
detected
Power supply warning detected as per PMBus STATUS_X reporting
bytes•
Power supply fault detected as per PMBus STATUS_X reporting
D1U54P-W-650-12-HBxC.A02 Page 3 of 9